SRC-C1T1 - Indoor CO2+Temperature Transmitter
The SRC-C1T1 is an indoor CO2 monitoring and temperature measuring
transmitter. Three LEDs in the colors green, orange and red indicate the CO2
concentration of the room air. This shows the user when to ventilate. The device
has two analog outputs and one relay output. The CO2 background calibration of
the SRC-C1T1 guarantees for accurate room air monitoring.
Features
Indoor CO2 and temperature measurement
Indication with three separate color LEDs
Minimum and maximum CO2 and temperature value memory
Two analog output signals for CO2 and temperature values
0...10 V or 2...10 V measuring analog output signal selectable with
jumpers
Relay output indicating CO2 concentration
Levels of CO2 indication programmable
Automatic CO2 background calibration
Output signal ranges programmable
May be used as simple P-controller
Averaging signal adjustable
Optional external display (OPA-S)
Status LED
Applications
Indoor CO2 and temperature measurement (home, office, school, restaurant, greenhouse, ...)
Recording of minimum and maximum CO2 and temperature limits for critical environments
Direct control of extraction fan
CO2 transmitter
The CO2 concentration is measured through non-dispersive infrared (NDIR) waveguide technology with ABC automatic
background calibration algorithm. The applied measuring technology guarantees excellent reliability and long-term
stability. The microprocessor samples the CO2 once per second. It calculates an averaging signal over a preset number of
samples and generates the output signal.
The analog output signal range may be customized by jumpers and if required by a programming module. Standard signal
ranges are 0...10 VDC and 2...10 VDC. Other ranges can be defined by using the external display and programming
module (OPA-S).
For OPA-S usage see section "Parameter configuration" on page 5.
Automatic baseline calibration (ABC)
The ABC background calibration constantly supervises the measured CO2 concentrations. The calibration function expects
the CO2 values sink to 400 ppm when the room is not occupied. Over a period of several days the controller tries to reach
this value step by step through recalibration of 30ppm per day max. In order to reach the given accuracy, it is required
that the sensor is for at least 3 weeks in operation.
NOTE: The ABC calibration works only in those applications where the CO2 concentration sinks regularly to fresh air
levels of 400 ppm. For special applications such as green houses, animal farms, etc. the ABC calibration should be
de-activated and the sensor should be manually calibrated. The automatic calibration can deactivate through the
external operation terminal. The Sensor can be calibrated by the client and does not need to be sent in for
calibration. For manual calibration see section "Calibration" on page 8.
Temperature transmitter
The temperature is measured with a precision sensing element. The microprocessor samples the temperature once per
second. It calculates an averaging signal over a preset number of samples and generates an analog output signal based
on a lower and an upper signal range value. Standard range is -40...60°C (-40...140°F) and 10 seconds average. The
measuring range and the averaging samples may be customized with the external display and programming module
(OPA-S).
The analog output signal range may be selected by jumpers and if required by a programming module. Standard signal
ranges are: 0...10 VDC and 2...10 VDC. Other ranges can be defined by using the external display and programming
module (OPA-S).
For OPA-S usage see section "Parameter configuration" on page 5.
Doc: 70-00-0794A, V2.7, 20210310
Subject to change without notice
CO2+T
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
T
EMPERATUR
RANSMITTER
SRC-C1T1
/M
ONITOR
Page 1-10

Advertisement

loading

Summary of Contents for Vector SRC-C1T1

  • Page 1 ONITOR SRC-C1T1 - Indoor CO2+Temperature Transmitter The SRC-C1T1 is an indoor CO2 monitoring and temperature measuring transmitter. Three LEDs in the colors green, orange and red indicate the CO2 concentration of the room air. This shows the user when to ventilate. The device has two analog outputs and one relay output.
  • Page 2 CO2+temperature transmitter / monitor Accessories OPA-S 40-500006 External display and programming module. Note: For the correct display of values, V1.7 and later is required. Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 2-10 Subject to change without notice www.vectorcontrols.com...
  • Page 3: Technical Specifications

    Declaration of Information on the conformity of our products can be found on our website Conformity www.vectorcontrols.com on the corresponding product page under "Downloads". Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 3-10 Subject to change without notice www.vectorcontrols.com...
  • Page 4 Areas with poor air circulation and niches, e.g., behind doors or shelves Outside walls insufficiently insulated In the direct influence area of ventilation openings and fans Mounting instruction See SRC-C1T1 installation sheet no. 70-000809 (www.vectorcontrols.com). Dimension mm (inch) Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland...
  • Page 5: Operation

    To read out or reset the stored CO2 and temperature minimum and maximum values use the optional display & programming module OPA-S. Remove SRC housing from the back plate (see SRC-C1T1 installation sheet no. 70-000809 www.vectorcontrols.com). Connect the OPA-S operating device to the OPA-S connector on the SRC (see section “Wiring and Connection” on page 4).
  • Page 6 If the default values are changed, the position of JP2 has no influence and the output signal range defined with the parameters applies. Input Parameter Output Parameter CO2 Input Temperature Input Analog Output Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 6-10 Subject to change without notice www.vectorcontrols.com...
  • Page 7 - 2 second blinking : Calibration - 10 second pulse : Calibration successful - Constant red > 10 sec : Calibration or sensor error Red Status-LED Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 7-10 Subject to change without notice www.vectorcontrols.com...
  • Page 8 IP 13 changes to 4. If unsuccessful, wait at least 1 minute before repeating the procedure again. Make sure that the sensor environment is steady and calm! Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 8-10 Subject to change without notice www.vectorcontrols.com...
  • Page 9 SRC-C1T1 CO2+T EMPERATUR RANSMITTER ONITOR Blank page. Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 9-10 Subject to change without notice www.vectorcontrols.com...
  • Page 10 SRC-C1T1 CO2+T EMPERATUR RANSMITTER ONITOR Smart Sensors and Controls Made Easy! Quality - Innovation – Partnership Vector Controls GmbH Switzerland info@vectorcontrols.com www.vectorcontrols.com/ Doc: 70-00-0794A, V2.7, 20210310 © Vector Controls GmbH, Switzerland Page 10-10 Subject to change without notice www.vectorcontrols.com...