Vacuum Mode - LG MULTI V S ARUN030GSS0 Installation Manual

Hide thumbs Also See for MULTI V S ARUN030GSS0:
Table of Contents

Advertisement

1,MFL67798030,영영 2018. 12. 7. 영영 1:37 Page 46
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
46

Vacuum Mode

This function is used for creating vacuum in the system after compressor replacement, ODU
parts replacement or IDU addition/replacement.
Vacuum mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"SVC" Push the '●' button
Select the Function using '▶', '◀' Button : :
"Se3" Push the '●' button
Start the vacuum mode : "VACC"
Vacuum mode off method
CAUTION
!
ODU operation stops during vacuum mode. Compressor can't operate.
ODU V/V open
ODU EEV open
IDU EEV open
Dip switch off and push the reset button on PCB
DIP SWITCH
7-Segment
SW04C ( X : cancel)
SW03C (
: forward)
SW02C (
: backward)
SW01C (
: confirm)
SW01D (reset)