7. CAPACITY TABLES

7-3. Correction by refrigerant piping length

CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. However, a decrease of cooling/
heating capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping
shown at 7-3-1 and 7-3-2, the capacity can be observed. 7-3-3 shows how to obtain the equivalent length of piping.
7-3-1. Cooling capacity correction
PQHY-P72ZLMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P96ZLMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P120ZLMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P144Z(S)LMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
MEES19K187
Total capacity of indoor unit
36
54
72
94
300
400
500
600 ft.
Total capacity of indoor unit
48
72
96
125
300
400
500
600 ft.
Total capacity of indoor unit
60
90
120
156
300
400
500
600 ft.
Total capacity of indoor unit
72
108
144
187
300
400
500
600 ft.
PQHY-P168Z(S)LMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P192Z(S)LMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P216ZSLMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
PQHY-P240ZSLMU
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
Piping equivalent length
WY-Series-575V
Total capacity of indoor unit
84
126
168
218
300
400
500
600 ft.
Total capacity of indoor unit
96
144
192
250
300
400
500
600 ft.
Total capacity of indoor unit
108
162
216
281
300
400
500
600 ft.
Total capacity of indoor unit
120
180
240
312
300
400
500
600 ft.
162