4.3 Circuit Protection

If the generator set circuit breaker trips or the fuses blow
repeatedly, see Section 4, Troubleshooting, for possible
causes.
4.3.1

Line Circuit Breaker

A line circuit breaker interrupts the generator output in
the event of a fault in the wiring between the generator
and the load. The line circuit breaker location is shown
in Figure 1-1. If the circuit breaker trips, reduce the load
and switch the breaker back to the ON position.
4.3.2

Fuses

The engine harness contains three 10-amp inline fuses.
Four additional fuses are located inside the junction box.
See the service views in Section 1 for the fuse locations
and Figure 4-2 for replacement fuse part numbers.
Always identify and correct the cause of a blown fuse
before restarting the generator set. Refer to section 4,
Troubleshooting, for conditions that may indicate a
blown fuse.
Obtain service from an authorized
distributor/dealer.
F1 Auxiliary Winding Fuse. A replaceable 10-amp
fuse protects the alternator.
F2 Relay Fuse. A replaceable 10-amp fuse protects the
engine relays. If the generator set does not crank, check
the battery and battery connections and then check the
relay fuse.
F3 Controller Fuse.
protects the controller circuitry. If the controller display is
dark, check the battery and battery connections and
then check the controller fuse.
Problem
Possible Cause
Controller LED
No power to the controller:
display is off
Continuous power mode jumper is
disconnected and the generator set has not
run for 48 hours or longer.
Controller fuse (F3) is blown.
Low or no battery voltage.
Generator set master switch is in the
OFF/RESET position.
Figure 4-3 ADC 2100 Troubleshooting Chart
32
Section 4 Troubleshooting
A replaceable 10-amp fuse
F4- -F7 Engine Fuses. See Figure 4-2 and the wiring
diagrams.
Fuse
Description
F1
10 Amp Auxiliary Winding
F2
10 Amp Relay Interface Board
F3
10 Amp Controller
15
Amp
Battery
Alternator
F4
F5 *
N/A *
F6
20 Amp Main Power Relay
F7
5 Amp ECM Power, Switched
* The F5 fuse is not used on the models covered by this
document.
Figure 4-2 Fuses

4.4 Fault Codes

The Advanced Digital Control displays fault codes to aid
in troubleshooting.
Fault codes, descriptions, and
recommended checks are listed in Figure 2-4.
Identify and correct the cause of the fault condition.
Then reset the controller after a fault shutdown. See
Section 2.3.5.

4.5 Troubleshooting

Figure 4-3 contains troubleshooting, diagnostic, and
repair information for the Advanced Digital Control.
Corrective Action
Controller display will automatically activate when a
remote start command is received or the generator
set master switch is moved to the RUN position.
See Section 2.3.6. Connect the jumper to maintain
continuous power to the controller, if desired.
Replace the fuse. If the fuse blows again, contact
the distributor/dealer.
Check connections.
Check generator set battery. See Figure 4-1.
Move generator set master switch to the AUTO or
RUN position.
Part Number
358337
223316
223316
Charging
283645
N/A *
GM39266
239298
TP-6197 3/06