Step 11 - Install Gas Piping; Factory Option Thru-Base Connections (Gas Connections) - Carrier WeatherMaster 48HC Series Installation Instructions Manual

Hide thumbs Also See for WeatherMaster 48HC Series:
Table of Contents

Advertisement

Step 11 — Install Gas Piping
Installation of the gas piping must be accordance with local
building codes and with applicable national codes. In U.S.A., re-
fer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC).
In Canada, installation must be accordance with the CAN/CSA
B149.1 and CAN/CSA B149.2 installation codes for gas burning
appliances.
This unit is factory equipped for use with natural gas (NG) fuel at
elevations up to 2000 ft (610 m) above sea level. Unit may be field
converted for operation at elevations above 2000 ft (610 m) and/or
for use with liquefied petroleum fuel. See accessory kit installation
instructions regarding these accessories.
NOTE: Furnace gas input rate on rating plate is for installation up
to 2000 ft (610 m) above sea level. In U.S.A., the input rating for
altitudes above 2000 ft (610 m) must be derated by 4% for each
1000 ft (305 m) above sea level. In Canada, the input rating must
be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft
(1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection
must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg
(3240 Pa) while the unit is operating. On 48HCF/N/T*05-06
(high-heat) units, the gas pressure at unit gas connection must
not be less than 5 in. wg (1245 Pa) or greater than 13 in. wg
(3240 Pa) while the unit is operating. See Table 3. For liquefied
petroleum applications, the gas pressure must not be less than
11 in. wg (2740 Pa) or greater than 13.6 in. wg (3390 Pa) at the
unit connection. See Table 4.
The gas supply pipe enters the unit at the burner access panel on
the front side of the unit, through the long slot at the bottom of the
access panel. The gas connection to the unit is made to the
FPT gas inlet port on the unit gas valve.
Manifold pressure is factory-adjusted for natural gas fuel use.
Adjust as required to obtain best flame characteristics. See
Tables 5 and 6.
Table 3 — Natural Gas Supply Line Pressure Ranges
UNIT MODEL
48HCD/E/L/M/S/R
48HCF/N/T
(High Heat Units Only)
Table 4 — Liquid Propane Supply Line Pressure
UNIT MODEL
48HCD/E/L/M/S/R
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODEL
48HCD/E/L/M/S/R
48HCF/N/T
(High Heat Units Only)
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT MODEL
48HCD/E/L/M/S/R
Downloaded from
ManualsNet.com
UNIT SIZE
MIN.
4.0 in. wg
13.0 in. wg
04, 05, 06
(996 Pa)
5.0 in. wg
13.0 in. wg
05, 06
(1245 Pa)
Ranges
UNIT SIZE
MIN.
11.0 in. wg
13.0 in. wg
04, 05, 06
(2737 Pa)
UNIT SIZE
HIGH FIRE
LOW FIRE
3.5 in. wg
04, 05, 06
(872 Pa)
3.5 in. wg
05, 06
(872 Pa)
UNIT SIZE
HIGH FIRE
LOW FIRE
10.0 in. wg
04, 05, 06
(2488 Pa)
search engine
EQUIPMENT DAMAGE
Failure to follow this caution may result in equipment damage.
When connecting the gas line to the unit gas valve, the installer
MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer
to the NFPA 54/NFGC or equivalent code for gas pipe sizing data.
Do not use a pipe size smaller than
to allow for a maximum pressure drop of 0.5 in. wg (124 Pa) be-
tween gas regulator source and unit gas valve connection when
unit is operating at high-fire flow rate.
The gas supply line can approach the unit in three ways: horizon-
tally from outside the unit (across the roof), through-curb/under
unit basepan (accessory kit required), or through unit basepan
(factory option or accessory kit required). Consult accessory kit
installation instructions for details on these installation methods.
Observe clearance to gas line components per Fig. 20.
BASE UNIT
1
/
-in.
2
BASE RAIL
FROM
GAS
METER
LEGEND
MAX.
National Fuel Gas
NFGC —
(3240 Pa)
Code
(3240 Pa)
STEEL PIPE NOMINAL
DIAMETERS (in.)
1-
MAX.
(3240 Pa)
(with Accessory Thru-the-Curb Service Connections)
FACTORY OPTION THRU-BASE CONNECTIONS (GAS
CONNECTIONS)
This service connection kit consists of a
1.7 in. wg
connector and a
(423 Pa)
an "L" bracket covering the embossed (raised) section of the unit
1.7 in. wg
basepan in the condenser section (see Fig. 21 for shipping posi-
(423 Pa)
tion). The
/
-in. bulkhead connector enables the low-voltage con-
3
4
trol wires to pass through the basepan. The
nector allows the high-voltage power wires to pass through the
basepan. See Fig. 22 and 23.
5.0 in. wg
(1244 Pa)
16
CAUTION
1
/
-in. Size the gas supply line
2
X
9" MINIMUM CLEARANCE
FOR PANEL REMOVAL
MANUAL GAS
*
SHUTOFF VALVE
48" MINIMUM
DRIP LEG
*
PER NFGC
ROOF
CURB
*Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
X DIMENSION (ft)
/
1
2
3
/
or 1
4
1
/
or larger
4
Fig. 20 — Gas Piping Guide
1
/
-in. electrical bulkhead
2
3
/
-in. electrical bulkhead connector, connected to
4
GAS
*
REGULATOR
FIELD-FABRICATED
*
SUPPORT
6
8
10
1
/
-in. bulkhead con-
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents