Installation Instructions

6 Refrigerant Line Routing

6.1 Precautions

Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For example:
When the refrigerant lines have to be fastened to floor joists or
other framing in a structure, use isolation type hangers.
Isolation hangers should also be used when refrigerant lines are
run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should
be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Side View
Figure 11
Side View
Figure 12
1 0 |
8 Feet Maximum
8 Feet Maximum
Secure Suction Line from joists using isolators every 8 ft. Secure Liquid Line
directly to Suction Line using tape, wire, or other appropriate method every 8 ft.
Isolation From Joist/Rafter
8 Feet Maximum
Secure Suction Line using isolators every 8 ft. Secure Liquid Line directly to
Suction Line using tape, wire, or other appropriate method every 8 ft.
Isolation On Walls
  Comply with National, State, and local codes when isolating linesets
from joists, rafters, walls, or other structural elements.
8 Feet Maximum
Bosch IDS BOVA15 Split System Heat Pump - BTC 761701317 A (02.2022)
Joist/Rafter
Isolator
Lineset
Wall
Isolator
Linesets