Circuit Breaker Failure Protection - Siemens SIPROTEC4 7SJ61 Manual

Communication module
Hide thumbs Also See for SIPROTEC4 7SJ61:
Table of Contents

Advertisement

DNP V3.00 Device Profile
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Name
>BLOCK 50Ns-2
220
>BLOCK 50Ns-1
221
>BLOCK 51Ns
222
>BLK 50Ns/67Ns
223
50Ns/67Ns OFF
224
50Ns/67Ns ACT
225
64 Pickup
226
64 Trip
227
50Ns-2 Pickup
228
50Ns-2 TRIP
229
50Ns-1 Pickup
230
50Ns-1 TRIP
231
51Ns Pickup
232
51Ns TRIP
233
Sens. Gnd block
234
Sens. Gnd Pickup
235
SensGnd undef.
236
Sens. Gnd Ph A
237
Sens. Gnd Ph B
238
Sens. Gnd Ph C
239
SensGnd Forward
240
SensGnd Reverse
241
>BLOCK 50BF
242
>50BF ext SRC
243
50BF OFF
244
50BF BLOCK
245
50BF ACTIVE
246
50BF int Pickup
247
50BF ext Pickup
248
50BF TRIP
249
50BF int TRIP
250
50BF ext TRIP
3-14
>BLOCK 50Ns-1; ON = 1, OFF = 0
>BLOCK 51Ns; ON = 1, OFF = 0
>BLOCK 50Ns/67Ns; ON = 1, OFF = 0
50Ns/67Ns is OFF; ON = 1, OFF = 0
50Ns/67Ns is ACTIVE; ON = 1, OFF = 0
64 displacement voltage pick up; ON = 1, OFF = 0
64 displacement voltage element TRIP; ON = 1, OFF = 0
50Ns-2 Pickup; ON = 1, OFF = 0
50Ns-2 TRIP; ON = 1, OFF = 0
50Ns-1 Pickup; ON = 1, OFF = 0
50Ns-1 TRIP; ON = 1, OFF = 0
51Ns Pickup; ON = 1, OFF = 0
51Ns TRIP; ON = 1, OFF = 0
Sensitive ground fault detection BLOCKED; ON = 1, OFF = 0
Sensitive ground fault pick up; ON = 1, OFF = 0
Sensitive Gnd fault direction undefined; ON = 1, OFF = 0
Sensitive Ground fault picked up in Ph A; ON = 1, OFF = 0
Sensitive Ground fault picked up in Ph B; ON = 1, OFF = 0
Sensitive Ground fault picked up in Ph C; ON = 1, OFF = 0
Sensitive Gnd fault in forward direction; ON = 1, OFF = 0
Sensitive Gnd fault in reverse direction; ON = 1, OFF = 0

Circuit breaker failure protection

BLOCK 50BF; ON = 1, OFF = 0
50BF initiated externally; ON = 1, OFF = 0
50BF is switched OFF; ON = 1, OFF = 0
50BF is BLOCKED; ON = 1, OFF = 0
50BF is ACTIVE; ON = 1, OFF = 0
50BF (internal) PICKUP; ON = 1, OFF = 0
50BF (external) PICKUP; ON = 1, OFF = 0
50BF TRIP; ON = 1
50BF (internal) TRIP; ON = 1, OFF = 0
50BF (external) TRIP; ON = 1, OFF = 0
Description
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
1203
3
1204
3
1207
3
1211
3
1212
3
1215
2
1217
2
1221
2
1223
2
1224
2
1226
2
1227
2
1229
2
1230
3
1271
2
1278
3
1272
2
1273
2
1274
2
1276
2
1277
2
1403
3
1431
3
1451
3
1452
3
1453
3
1456
2
1457
2
1471
2
1480
2
1481
2
C53000-L1840-A001-01