FS20X Fire and Flame Detectors

Specifications

Mechanical

Description
copper-free aluminum (red)
Enclosure Materials
316 stainless steel
Assembly
4�35 in� (110�49 mm) H × 4�81 in� (122�24 mm) Dia
Dimensions
Mounting holes ¼ in� (6�35 mm) Dia, 5½ in� (139�70 mm) center-to-center
Conduit entries Two ¾ in� NPT or two 25 mm
Aluminum
3 lbs� 11 oz� (1�7 kg) approximately
Weight
Stainless steel
7 lbs� 7 oz� (3�4 kg) approximately
Enclosure Rating
IP66, NEMA 4, NEMA 4X
Vibration
meets or exceeds Mil Spec 810C, Method 514�2, Curve AW

Electrical

Description
Input voltage range
18 VDC to 32 VDC
Normal operation current
85 mA (nominal), 175 mA (nominal with heater
Maximum fire alarm current
135 mA (maximum), 220 mA (maximum with heater
Relay contact rating
1 Amp @ 24 VDC resistive
0�0 to 20�0 mA (Non-isolated source or sink, user selectable)
0�0 mA (<0�6 mA) = Fault
2�0 mA (±0�6 mA) = Dirty window
4�0 mA (±0�6 mA) = Normal, safe (no fault, no fire)
2, 3
Analog current output
8�0 mA (±0�6 mA) = Background IR
12�0 mA (±0�6 mA) = Background UV
16�0 mA (±0�6 mA) = Fire alarm
20�0 mA (±0�6 mA) = Verified fire alarm
Screw terminal wire sizes
12 AWG to 22 AWG (2�50 mm to 0�762 mm; use stranded
conductors, not solid core)
1
The heater circuit turns on only when the temperature drops below 0° F (-17° C)�
2
400 ohms maximum load (loop resistance)
3
If the "verify time" is not zero, the alarm level = 16 mA and the verify level = 20 mA� If the verify time
is zero, alarm level = 20 mA and the verify level = 20 mA�
Value
Value
1
)
1
)
34
FS20X Fire and Flame Detectors

Environmental

Description
Operating Temperature,
-40° F to +185° F (-40° C to +85° C)
Standard
Operating Temperature,
-14
F to +131
F (-10
o
o
EN54-10
(full range of EN54-10)
Operating Humidity Range
0 to 95% RH, 100% RH condensing for short periods of time
Storage Temperature
-67° F to +221° F (-55° C to +105° C)

Performance

Description
cone of view is 90° horizontal and 80° vertical (35° above
Field of View
the center line and 45° below it)
Sensitivity
1 sq� ft� heptane fire at 200 feet (± 45° from axis)
Speed of Response
typically 2 to 5 seconds
Spectral Sensitivity
~0�185 to 0�26 microns and 0�4 microns to 3�5 microns
must be rated at least 10°C above the rated service temperature
Wire Temperature Rating
(120°C for T4 applications, 85°C for T5 applications)

Exteneded Field of View

Description
Field of View
±60 vertical and horizontal
Sensitivity
1 sq� ft� heptane fire at 40 feet = 7 seconds (or less)
Sensitivity
2 in� diameter IPA fire at 3 feet = 3�5 seconds (or less)

Hazardous Area Classifications

(See
"Hazardous Location Detector Markings" on page
Description
Class I, Division 1, Groups A, B, C & D
Class II, Division 1 Groups E, F & G
Class I, Zone 1, AEx d/ Ex d IIC
Class III Ex db IIC, Ex tb IIIC
T4: Ta = -40°C to +110°C
T4: Ta = -40°C to +110°C
T5: Ta = -40°C to +75°C
T5: Ta = -40°C to +75°C
T6: Ta = -40°C to +60°C
T6: Ta = -40°C to +60°C

Performance Certifications

(See
"Hazardous Location Detector Markings" on page
Value
C to +55
C)
o
o
Value
Value
37)
37)
35