TECHNICAL DATASHEET
LYTE II DIN Rail Power Supply
DRL-120W series / DRL-V120W1EN
Model Number
Reliability Data
MTBF
Expected Cap Life Time
Safety Standards / Directives
Electrical Safety
CE
UKCA
Galvanic Isolation
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
4
www.DeltaPSU.com (March 2022, Rev. 03)
DRL-12V120W1EN
Telcordia
> 700,000 hrs
SR-332
I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C
10 years (230 Vac, 50% load @ 40°C)
CB scheme
IEC 62368-1, IEC 60950-1, IEC 61010-1 & -2-201
TUV Bauart
EN 62368-1, EN 61010-1 & -2-201
UL/cUL
UL 62368-1
BSMI
CNS14336-1
EAC
TP TC 004/2011
KC
K 60950-1 (24 V model only)
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
In conformance with Electrical Equipment (Safety) Regulations 2016 and Electromagnetic
Compatibility Regulations 2016
Input to
3.0 KVac
Output
Input to
2.0 KVac
Ground
Output to
1.0 KVac
Ground
DRL-24V120W1EN☐
DRL-48V120W1EN