Download Print this page

Press The; Use The - Honeywell T775U Series Installation Instructions Manual

2000 electronic stand-alone controller
Hide thumbs Also See for T775U Series:

Advertisement

1. SETUP
SETUP
SENSORS
SENSOR A
TYPE
Fig. 27. Setup - Sensors - Sensor A - Type.
SETUP
SENSORS
SENSOR A
UNITS
Fig. 28. Setup - Sensors - Sensor A - Units.
SETUP
SENSORS
SENSOR A
UNITS
Fig. 29. Setup - Sensors - Sensor A - Units.
All manuals and user guides at all-guides.com
1.2.2.1. TYPE
SETUP
SENSORS
1. From the Sensor A selections, use the
SENSOR A
TYPE

2. Press the

PT 1000
0-5V

3. Use the

0-10V
4-20MA
NOTE: The default label PT1000 refers to a 1097Ω PTC
SELECT
TYPE FOR
4. Press the
SENSOR A
M24589A
5. For PT1000 (1097Ω PTC) temperature sensors, go
SETUP
1.2.2.2.1. UNITS
SENSORS
SENSOR A
If Sensor A is configured for °F or °C units, then the units
UNITS
selection does not appear for Sensor B, since Sensor B
DEG F
uses the units specified for Sensor A.
DEG C
1. From the Sensor A selections, use the
2. Press the
3. Use the
4. Press the
SELECT
UNITS FOR
SENSOR A
M24590
Continue with "1.2.2.3. CALIBRATE (Sensor A or B)".
SETUP
1.2.2.2.2. UNITS
SENSORS
SENSOR A
1. From the Sensor A selections, use the
UNITS
DEG F
DEG C
2. Press the
PSI
3. Use the
IN WC
% RH
PA
KPA
PPM
NONE
4. Press the
SELECT
UNITS FOR
SENSOR A
M24591A
15
T775U SERIES 2000 CONTROLLER
(Sensor A only)
buttons to highlight TYPE.
button to display the type values.
and
buttons to highlight the desired
value PT1000 (1097Ω PTC), 0-5V, 0-10V, or 4-
20MA.
Default: PT1000
temperature sensor.
button to accept the units and return to
the Sensor A selections.
to "1.2.2.2.1. UNITS (Sensor A or B; PT1000
[1097W PTC)]".
For 0-5V, 0-10V, and 4-20MA sensors, go to
"1.2.2.2.2. UNITS (Sensor A only; 0-5V, 0-10V, or 4-
20mA)"
(Sensor A or B; PT1000 [1097Ω PTC)]
buttons to highlight UNITS.
button to display the temperature units.
and
buttons to highlight F or C.
Default: F (Fahrenheit)
button to accept the units and return to
the Sensor A selections.
(Sensor A only; 0-5V, 0-10V, or 4-20mA)
buttons to highlight UNITS.
button to display the units list.
and
buttons to scroll through the list
and highlight the desired unit of measure.
You may need to scroll up or down to view all units.
Default: F (Fahrenheit)
button to accept the units and return to
the Sensor A selections.
and
and
and
62-0255–05

Advertisement

loading

This manual is also suitable for:

T775u2006T775u2016