Greenheck SQ-7 Quick Start Manual page 2

Mixed flow square duct adapter

Advertisement

Quick Start Guide
SQ Mixed Flow Filtration
Filtration Quick Start Guide
Filter Sections are shipped separate from the fan
and are mounted in the field
This Quick Start Guide does not replace the
Installation Operation Manual (IOM), refer to the
IOM for more information
Parts and Tools List
Parts List
(1) Fan
(1) Filter section
(1) Hardware kit
(2) Isolator kit (optional)
Tool List
Impact
1/2 inch socket
Torque wrench
NOTE: Square Duct Adapter information on reverse side
Step 1
Mount Filter Section to Fan
Filter section and fan have "Airflow" decals on
the exterior of the units, ensure the arrows are
aligned with the airflow
Mount the filter section to the inlet of the fan
using appropriate number of provided 5/16 inch
semi-gimlet fasteners provided in hardware kit
(no nuts required)
Tighten to 132 in∙lbs (11 ft·lbs) as specified in
the IOM with 1/2 inch socket DO NOT
OVER-TIGHTEN
Fan sizing and performance is designed for the
filter section to be mounted directly to the
INLET of the fan
Step 2
Install Filter and Fan Assembly in Ductwork
Install assembly in proper orientation for
application (use appropriate isolators)
Mount assembly to ductwork using fasteners
supplied by others
Assembly can be mounted in horizontal or
vertical applications
Flexible duct connectors are recommended for
mounting to the inlet of the filter section and
outlet of the fan
Install assembly with approximately three wheel
diameters of straight duct before and after
the fan
Filter Replacement and Cleaning
Follow filter replacement and or cleaning
intervals recommended by filter supplier
1. Remove access door using 1/2 inch socket
It is only necessary to remove one access
door to replace filters
2. Remove filter spacers and dirty filters
3. Install new filters in unit and replace filter spacers
Ensure filters are installed in correct
orientation for proper airflow (marked
on filters)
Locate spacers towards the outside of the
unit to reduce any unnecessary blockage
in airflow
4. Reinstall access door using 1/2 inch socket,
FILTER(S)
torque to 132 in∙lbs (11 ft·lbs) DO NOT
OVER-TIGHTEN