The following information should be used for determining the proper location of the vent
terminal for direct vent tankless water heaters .
A= Clearance above grade, veranda,
porch, deck or balcony .
B= Clearance to window or door that
may be opened .
C= Clearance to permanently closed
window .
D= Vertical Clearance to ventilated
soffit located above the terminal
within a horizontal distance of 2
feet (61 cm) from the center line of
the terminal .
E= Clearance to unventilated soffit .
F= Clearance to outside corner .
G= Clearance to corner .
H = Clearance to each side of center line
extended meter/regulator assembly .
above
I = Clearance to service regulator
coaxial vent outlet .
J = Clearance to nonmechanical air
supply inlet to the combustion
air inlet to any building or other
appliance .
K = Clearance to mechanical air supply
inlet .
L = Clearance above paved sidewalk or
paved driveway located on public
property .
M = Clearance under veranda, porch,
deck or balcony .
1
In accordance with current CSA-B149 .1 Installation Codes .
2
In accordance with current ANSI Z223 .1/ NFPA 54 National Fuel Gas Code .
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
dwellings and serves both dwellings .
*
For clearances not specified in ANSI 223 .1/NFPA 54 or CSA-B149 .12, one of the following shall be indicated:
a)
A minmum clearance value determined by testing in accordance with section 2 .20, or;
b)
A reference to the following footnote: "Clearance in accordance with local installtion codes and the require-
ments of the gas supplier ."
area Where terminal iS nOt permitted
Canadian installations
1
12 inches (30 cm) above anticipated
snow level .
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3kW) and <
100,000 Btuh (30kW), 36 inches (91 cm)
for appliances > 100,000 Btuh (30kW) .
*
*
*
*
*
3 feet (91 cm) within a height 15 feet
(4 .57 m) above the meter/regulator
assembly .
3 feet (91 cm)
6 inches (15 cm) for appliances <
10,000 Btuh (3 kW), 12 inches (30 cm)
for appliances > 10,000 Btuh (3kW)
and < 100,000 Btuh (30kW), 36 inches
(91 cm) for appliances > 100,000 Btuh
(30kW) .
6 feet (1 .83 m)
7 feet (2 .13 m)†
Not Allowed
uS installations
2
12 inches (30 cm) above anticipated
snow level .
6 inches (15 cm) for appliances <
10,000 Btuh (3 kW), 9 inches (23 cm)
for appliances > 10,000 Btuh (3kW)
and < 50,000 Btuh (15kW), 12 inches
(30 cm) for appliances > 50,000 Btuh
(15kW) .
*
*
*
*
*
*
*
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 9 inches (23 cm) for
appliances > 10,000 Btuh (3kW) and <
50,000 Btuh (15kW), 12 inches (30 cm)
for appliances > 50,000 Btuh (15kW) .
3 feet (91 cm) above if within 10 feet
(3 m) horizontally .
*
Not Allowed
11