Diagnostics Led - tau D703M Instruction Manual

Control panel for 230/400vac single/three-phase motor
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
Clock function:
A timer can be connected to the open-close pushbutton in order to keep the gate open at certain
times during the day, after which it reverts to automatic closing.
DL1
STOP button green LED signal
DL2
PEDESTRIAN button red LED signal
DL3
STEP BY STEP button red LED signal
DL4
OPEN button red LED signal
DL5
CLOSE button red LED signal
DL6
SENSITIVE EDGE green LED signal
DL7
PHOTOCELL green LED signal
DL8
CLOSE LIMIT SWITCH green LED signal
DL9
OPEN LIMIT SWITCH green LED signal
1_ The automation does not start
a_ Check there is 230Vac power supply with the multimeter;
b_ Set the SW1 jumper on the correct available voltage;
c_ Check that the NC contacts of the card are actually normally closed (5 green LEDs on);
d_ Set the dip 3 (man present function) to OFF, dip 5 (encoder) to ON, dip 6 (phototest) to
OFF;
e_ Check that the fuses are intact with the multimeter.
2_ The radio control has very little range
a_ Connect the radio aerial to the terminals of the receiver card and not to terminals 31-32 of
the control card (for frequency 433,92 MHz);
b_ Check that the ground and the aerial signal connections have not been inverted;
c_ Do not make joints to increase the length of the aerial wire;
d_ Do not install the aerial in a low position or behind walls or pillars;
e_ Check the state of the radio control batteries.
3_ The gate opens the wrong way
a_ Invert the motor connections on the terminal block (terminals 5 and 6);
Consequently, invert the connections of the limit switches (terminals 20 and 21).
MALFUNCTIONS: POSSIBLE CAUSES AND SOLUTION
D703M

DIAGNOSTICS LED

15