S82K
J INRUSH CURRENT, RISE TIME, HOLD TIME
Input ON
AC input
voltage
Inrush current on input application
AC input
current
Output
voltage
Rise time: 100 to 1000 ms
max. depending on the
model.

Operation

J UNDERVOLTAGE ALARM INDICATOR AND OUTPUT FUNCTION
(ALL MODELS EXCEPT S82K-24024/P24024)
If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K (DC LOW indicator) will
be lit. In the case of the S82K-10024/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output).
This function detects the voltage at the output terminal of the Power Supply. To check the precise output voltage, measure the voltage at
the terminal of the load.
Indicator
Green:
DC ON
Red:
DC LOW
Green:
DC ON
(see note 1)
Red:
DC LOW
Green:
DC ON
Red:
DC LOW
Note: 1. The more the voltage at the output terminal drops, the darker both the green and red indicators will be.
2. The relay contacts have a capacity of 0.1 A at 24 VDC.
Input OFF
90%
Hold time
(20 ms min.)
Voltage
If the voltage at the output terminal is more than 90%
of the rated voltage, the green indicator will be lit.
If the voltage at the output terminal is 75% to 90%,
the red indicator will be lit.
If the voltage at the output terminal is 0 V, both the
green and red indicators will not be lit.
96.5%
Operation of 09024/10024/24024T's
output (DC LOW output)
(see note 2)