Refrigerant System Pressure Access Ports - Carrier 48JC04-06 Service And Maintenance Instructions

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

CLAMP
TXV SENSING
BULB
SENSING BULB INSULATION REMOVED FOR CLARITY
Fig. 17 — TXV Valve and Sensing Bulb Location
5/8" HEX
1. CoreMax is a registered trademark of Fastest, Inc.
THERMAL EXPANSION
(TXV) VALVE
SEAT
1/2-20 UNF RH
0.596
30°
0.47
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 18 — CoreMax

Refrigerant System Pressure Access Ports

There are two access ports in the system: on the suction tube
near the compressor and on the discharge tube near the com-
pressor. These are brass fittings with black plastic caps. The
hose connection fittings are standard 1/4-in. SAE male flare
couplings.
The brass fittings are two-piece high flow valves, with a recep-
tacle base brazed to the tubing and an integral spring-closed
check valve core screwed into the base. See Fig. 18. This check
valve is permanently assembled into this core body and cannot
be serviced separately; replace the entire core body if neces-
sary. Service tools are available from RCD that allow the re-
placement of the check valve core without having to recover
the entire system refrigerant charge. Apply compressor refrig-
erant oil to the check valve core's bottom o-ring. Install the fit-
ting body with 96 ± 10 in.-lb (10.85 ± 1.1 Nm) of torque; do
not over-tighten.
CORE
(Part No. EC39EZ067)
WASHER
O-RING
1/2" HEX
1
Access Port Assembly
11
45°
DEPRESSOR PER AHRI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH