Carrier 48MA/50ME016-040 Installation, Start-Up And Service Instructions Manual page 26

Combination multizone heating/cooling units gas, electric, or glycol heat
Table of Contents

Advertisement

LEGEND
C
— Contactor
CR
— Control Relay
GV
— Gas Valve
HA
— Heat Anticipator
HR
— Heating Relay
TC
— Thermostat, Cooling
TH
— Thermostat, Heating
TRAN — Transformer
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 21 — 50ME; Two-Stage Heat, Two-Stage Cool — 2 Modules, Joint Zone Control
*One for each module.
NOTES:
1. COOLING
Stage 1 — First stage of modules 1 and 2
Stage 2 — Second stage of modules 1 and 2
HEATING
Stage 1 — First stage of modules 1 and 2
Stage 2 — Second stage of modules 1 and 2
2. Set heat anticipator 1 (HA1) at .26, and set heat anticipator 2 (HA2)
at 1.14.