Outdoor Air Quality Sensor; Smoke Detector/Fire Shutdown (Fsd) - Carrier 50HCQA User Manual

Single package rooftop heat pump with puron (r-410a) refrigerant
Table of Contents

Advertisement

H G 24 VAC
OR
+ -
24 VDC
2 1
8 7 6 5 4 3 2 1
J3
J4
Fig. 38 - - Indoor/Outdoor Air Quality (CO
(33ZCSENCO2) - - Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return- - air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2- - conductor 18 AWG (American Wire Gage)
twisted- - pair cables (unshielded) to connect the separate
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 38. Connect the 4- - 20 mA terminal to
terminal TB1- - 9 and connect the SIG COM terminal to
terminal TB1- - 11. See Fig. 39.
IAQ Sensor
SEN
COM
24 VAC
Fig. 39 - - Indoor CO
2
Connections
+
0-10VDC
-
SIG COM
+
4-20mA
NC
}
ALARM
COM
RELAY
NO
CONTACTS
C08635
) Sensor
2
TB1
PL
9
J5-5
TB1
J5-3
11
C08636
Sensor (33ZCSENCO2)
Refer to Form 33CS- - 58SI, PremierLink Installation,
Start- - up, and Configuration Instructions, for detailed
configuration information

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
2
dioxide (CO
) levels in the outside ventilation air and
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 40. The outdoor air CO
economizer outside air hood.
2
COVER REMOVED
Fig. 40 - - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
power supply is required for this sensor. A two- - wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect the 4 to 20 mA
terminal to the TB1- - 13 terminal of the 50HCQ. Connect
the SIG COM terminal to the TB1- - 11 terminal of the
50HCQA. See Fig. 41.
OAQ Sensor/RH Sensor
SEN
COM
24 VAC
Fig. 41 - - Outdoor CO
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is
configured for (Space) Sensor Mode. The unit is
factory- - wired for PremierLink FSD operation when
PremierLink is factory- - installed.
23
sensor is designed to monitor carbon
sensor must be located in the
2
SIDE VIEW
Sensor: A dedicated
2
TB1
13
TB1
11
Sensor Connections
2
C07135
PL
J5-2
J5-3
C08275