or an equivalent protective covering. Cap open ends of pipes
stored on the jobsite. This precaution is especially important in
areas where painting, plastering, or spraying of fireproof mate-
rial, etc. is not yet complete. Foreign material that accumulates
within the units can prevent proper start-up and necessitate
costly clean-up operations.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Verify that the unit is the correct model for the entering
water temperature of the job.
50PCH,PCV UNIT
COMPRESSOR (1 each)
REFRIGERANT TYPE
Factory Charge (oz)
FAN MOTOR AND BLOWER
Fan Motor Type/Speeds
Fan Motor (hp)
Blower Wheel Size (Dia x W) (in.)
COAX VOLUME (gal.)
WATER CONNECTION SIZE FPT (in.)
HORIZONTAL
Air Coil Dimensions (H x W)(in.)
Standard Filter - (Qty)
1 in. Throwaway
Weight (lb)
Operating
Packaged
Corner Weight (lb)*
Left-Front
Right-Front
Left-Back
Right-Back
VERTICAL
Air Coil Dimensions (H x W)(in.)
Standard Filter - (Qty)
1 in. Throwaway
Weight (lb)
Operating
Packaged
LEGEND
FPT — Female Pipe Thread
PSC — Permanent Split Capacitor
Table 1 — Physical Data — 50PCH,PCV Units
006
009
012
015
Rotary
17
18.5
23
32
1
1
1
1
/
/
/
25
10
10
5 x 5
6 x 5
0.123
0.143
0.167
0.286
1
/
2
10 x 15
(1) 10 x 18
103
105
114
153
113
115
124
158
37
38
42
53
24
24
26
36
23
23
25
34
19
20
21
30
10 x 15
(1) 10 x 18
103
105
114
153
113
115
124
158
3
3. Do not remove the packaging until the unit is ready for
installation.
4. Verify that the refrigerant tubing is free of kinks or dents,
and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are
clean and tight at the terminals.
6. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
7. Remove the four
1
support plate (two bolts on each side) to maximize vibra-
tion and sound alternation.
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
8. Remove any blower support cardboard from inlet of the
blower.
9. Locate and verify any accessory kit located in compressor
section.
10. Remove any access panel screws that may be difficult to
remove once unit is installed.
018
024
030
R-410A
43
43
47
PSC/3
1
1
3
/
/
/
/
6
6
4
4
8 x 7
9 x 7
0.450
0.286
0.323
16 x 22
(1) 16 x 25
(1) 18 x 25
158
174
182
163
179
187
55
62
67
37
40
41
35
39
40
31
33
34
20 x 17.25
(1) 20 x 20
158
189
197
163
194
202
*Front is located at control box end.
NOTES:
1. All units have grommet compressor mountings, and
3
/
-in. electrical knockouts.
4
2. Maximum water working pressure is 500 psig.
/
in. shipping bolts from compressor
4
CAUTION
036
042
048
Scroll
50
70
74
1
3
3
/
/
/
2
4
4
9 x 8
10 x 10 11 x 10
0.323
0.890
0.738
3
/
4
20 x 25
20 x 35
(1) 20 x 28 or
(1) 20 x 24,
(2) 20 x 14
(1) 20 x 14
203
218
263
209
224
270
75
81
98
47
50
60
44
48
58
37
39
47
24 x 17.75
24 x 28.25
(1) 14 x 24,
(1) 24 x 24
(1) 18 x 24
203
218
263
209
224
270
060
82
1
0.939
1
278
285
103
64
61
75
278
285
1
/
-in. and
2