[ VII Troubleshooting ]
VII Troubleshooting

[1] Troubleshooting

1. Check methods

1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Water inlet thermistor (TH22)
Water outlet thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a volt meter.
(Ambient temperature 10°C - 30°C)
Normal
4.3kΩ - 9.6kΩ
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
Room temperature thermistor (TH21)
Water inlet pipe thermistor (TH22)
Water outlet thermistor (TH23)
Drain sensor (DS)
Thermistor R
= 15 kΩ 3%
0
Multiplier of B = 3480 kΩ 2%
Rt = 15 exp { 3480(
0°C 15kΩ
10°C 9.6kΩ
20°C 6.3kΩ
25°C 5.2kΩ
30°C 4.3kΩ
40°C 3.0kΩ
(A) Temperature
(B) Resistance
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Flow control valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
CN8A
(H)
1
(G)
2
(F)
3
(E)
4
M
(D)
5
(C)
6
(B)
FCV
7
(A)
8
(A)
Yellow
(B)
White
(C) Black
(D) Brown
HWE18200
Abnormal
Open or short
1
1
) }
273+t
273
(°C)
(kΩ)
1-5
2-5
Purple-Brown
Orange-Brown
(E)
Green
(F)
Blue
(G)
Orange
(H)
Purple
50
40
30
20
10
0
-20
-10
0
10
(A)
Normal
3-5
Blue-Brown
55Ω / PHASE
- 24 -
20
30
40
50
Abnormal
4-5
Open or short
Green-Brown
GB