SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical com-
ponents, and equipment location.
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on air-conditioning equipment, observe
precautions in the literature and on tags, stickers, and labels at-
tached to the equipment.
Follow all safety codes. Wear safety glasses and work
gloves. Use care in handling equipment.
Be sure power to equipment is shut off before performing
maintenance or service to avoid electrocution. Lock out
and safety-tag all disconnects. There may be more than one
disconnect.
GENERAL
This control accessory reduces 30XA chiller capacities be-
low the standard lowest capacity step. This capacity reduction
provides more precise control of leaving fluid temperature
during light load conditions.
The minimum load control solenoid valve limits the amount
of gas that can be bypassed from the condenser without
impacting oil return.
One accessory package is required for 30XA080-350 units.
Two accessory packages are required for 30XA400-500 units
to accommodate connections for three refrigerant circuits. See
Table 1 for accessory package usage.
Table 1 — Accessory Package Usage
30XA UNIT SIZE
080-240
260-300
325, 350
400
450, 500
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300010-01
Book 2
Tab
5c

Installation Instructions

ACCESSORY PART NO.
00EFN9000002700A
00EFN9000002800A
00EFN9000002900A
00EFN9000002700A,
00EFN9000002800A
00EFN9000002800A,
00EFN9000002900A
Printed in U.S.A.
Minimum Load Control Accessory
INSTALLATION
Examine the package contents for correct part numbers. If
any of the components are damaged, file a claim with the
shipping company and notify your Carrier representative.
See Table 2A, 2B, or 2C for package contents. See Fig. 1 for
dimensional drawings of tubes included in the kit.
The following material is field supplied:
5
/
in. OD copper tubing
8
5
/
in. OD copper tube elbows and couplings
8
(as required)
• Loctite 554 thread sealing compound
• Parker Super O-lube O-ring lubricant
Install the Solenoid Valve Tube Assembly
1. Remove refrigerant charge from the circuits using an
approved refrigerant recovery device before proceeding
with this installation. Follow good piping practices.
2. Locate the discharge manifold for minimum load
piping on the side of the coil V for each circuit as
shown in Fig. 2. Locate the
the top of the cooler for each circuit. See Fig. 3.
3. Remove the
1
/
in. NPT pipe plugs from the top of the
2
cooler. Use the thread sealing compound and install
one 1 in.-14 O-ring seal (ORS) x
for each circuit. Lightly lubricate each O-ring with
O-lube and attach the tube assembly to each adapter.
See Fig. 3. Be sure to attach the correct tube assembly
to the cooler. Refer to the usage column in Tables 2A,
2B, and 2C for tube assembly part number correspond-
ing to the unit size and circuit. The nut on the tube
assembly should be torqued to 30 ft-lb (40 N-m).
4. Remove the trim panel on the discharge manifold for
minimum load piping on the side of the coil V. Use a
tubing cutter to cut 1
fold for each circuit. See Fig. 4. Braze a tee in between
the gap and, depending on the routing of the hot gas
bypass tubing, have the tee's remaining port facing either
left or right.
5. Use field-supplied
(as required) to pipe from the solenoid valve outlet to the
5
/
in. port of the tee on the discharge manifold. Use the
8
provided
5
/
in. tubing clamps to secure the tubing to the
8
unit frame as necessary.
6. When piping is completed, leak test the assembly.
7. Evacuate, dehydrate, and recharge each circuit. Be sure to
use the correct type and amount of refrigerant listed in the
nameplate data and base unit documentation.
8. Restore power to the unit.
Form 30XA-6SI
Pg 1
30XA080-500
1
/
in. NPT pipe plugs on
2
/
in. NPT adapter
1
2
1
/
in. out from the discharge mani-
2
5
/
in. OD copper tubing and fittings
8
12-06
Replaces: New

Advertisement

loading

Summary of Contents for Carrier MINIMUM LOAD CONTROL ACCESSORY 30XA080-500

  • Page 1: Installation Instructions

    Examine the package contents for correct part numbers. If any of the components are damaged, file a claim with the shipping company and notify your Carrier representative. See Table 2A, 2B, or 2C for package contents. See Fig. 1 for dimensional drawings of tubes included in the kit.
  • Page 2 Table 2A — Contents of Accessory Kit, Part No. 00EFN900002700A PART NUMBER QUANTITY 00PSN500171700A ball valve, and 90 degree bend tube assembly 30GX5034892 00PPG000011600A KA66AA062 DE40BA705 TH70400410 00PPN500000401A 32GB500432E TH70400864 HH83ZB001 A6X10004352 A6X10004434 TH70400852 HY89TB010 LEGEND HGBP — Hot Gas Bypass —...
  • Page 3 Table 2C — Contents of Accessory Kit, Part No. 00EFN900002900A PART NUMBER QUANTITY Tube assembly including solenoid valve, 00PSN500175200A ball valve, and 90 degree bend tube assembly 30GX5034892 00PPG000011600A KA66AA062 DE40BA705 TH70400410 00PPN500000401A 32GB500432E TH70400864 HH83ZB001 A6X10004352 A6X10004434 TH70400852 HY89TB010 LEGEND HGBP —...
  • Page 4 a30-4498...
  • Page 5 1/2 IN. NPT A CIRCUIT B CIRCUIT 1/2 IN. NPT TUBE ASSEMBLIES a30-4501 Fig. 3 — Typical Solenoid Valve Tube Assembly Installation BRAZE THE TEE IN THIS LOCATION CUT 1-1/2 IN. OFF THE DISCHARGE MANIFOLD REMOVE TRIM PANEL TO ACCESS a30-4502 Fig.
  • Page 6 Install HGBP/Pump Board and Control Wiring 1. Attach the solenoid coil assembly to the solenoid valve plunger on the tube assembly for each circuit. One cable assembly TH70400410 is supplied per circuit. Secure the DIN connector end on the solenoid valve coil with the screw in the connector.
  • Page 7 Fig. 6B — HGBP/Pump Board and CB14 Mounting Location (30XA080-120: 460 v, 575 v) TB10-X2 OR TB11-X2 CB14 3.2 AMPS TB10-X1 OR TB11-X1 Fig. 7 — HGBP/Pump Board 24 v Power Wiring TOUCH PILOT DISPLAY CB14 FIOP/ACCESSORY HGBP/ PUMP BOARD a30-4506 HGBP/PUMP BOARD...
  • Page 8 Controls, Start-Up, Operation, Service, and Troubleshooting manuals to verify proper operation of the solenoid(s). Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300010-01...