2.4
Terminal board connections
+
-
1 2 3 4 5 6 7 8 9 10 11 12
Factory setting
Electrical supply: 230V
Input signal: 0/4 – 20mA
2.5
Input signal
SERVOMOTOR POSITION
100%
20%
0%
The input signal can be easy adapted to the stroke of the servo-
motor as shown below:
4
20mA
they correspond to
–
2
10V
they correspond to
–
or for other applications:
0
20mA
they correspond to
–
0
10V
they correspond to
–
2.6
E 5202 Converter adjustment
The converter does not require specific calibration; it adapts
the position of the servomotor to the 0/4to20mA (or 0/
2to10V) input signal through combination with the potenti-
ometer's resistance value.
The converter is fitted with a trimmer (Dead Band) posi-
tioned on the front panel; you are anyway recommended to
regulate the trimmer to the maximum value, (TRIM fully
rotated clockwise), to avoid a a reaction that is too frequent
with needless repositioning of the servomotor in the case of
very small variations of the input signal.
The maximum value of the Dead Band is 1%, that corre-
sponds to no repositioning reaction until the input variation
signal is more than 0.2 mA (or 0.1V) (angle of around 1°).
•
Signal converter kit
INC.
DEC.
Maximum power output
Minimum power output
Stop
0
0
MIN servomotor position - to the MAX servomotor position
(MIN power output
See diagram.
MIN servomotor position - to the MAX servomotor position
(MIN power output
See diagram.
Servomotor closure position
See diagram.
Servomotor closure position
See diagram.
+
1 2 3 4 5 6 7 8 9 10 11 12
Optional signals (only if necessary)
In the case of 115V electrical supply move the wire
from clamp 10 to clamp 11.
In the case of the 0/2 – 10V input signal move the
jumper onto clamp V.
4
2
INPUT SIGNAL
MAX power output)
–
MAX power output)
–
MAX servomotor position
–
MAX servomotor position
–
3
GB
INC.
DEC.
-
20
[mA]
[V]
10
Fig. 2
Fig. 3
2916224