Optional Economi$Er Iv And Economi$Er2 - Carrier 50HE003-006 Installation Instructions Manual

Single-package rooftop electric cooling units with optional electric heat
Table of Contents

Advertisement

1. Use a 4-conductor, 18 or 20 AWG cable to connect the
enthalpy control to the PremierLink™ controller and
power transformer.
2. Connect the following 4 wires from the wire harness
located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1) on
enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal (TR)
on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on PremierLink
controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on PremierLink
controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires
provided from the control section to the economizer to connect
PremierLink controller to terminals 2 and 3 on enthalpy sensor.
Return Air Enthalphy Sensor
Mount the return-air enthalpy sensor (HH57AC078) in the
return-air duct. The return air sensor is wired to the enthalpy
controller (HH57AC077). The outdoor enthalpy changeover set
point is set at the controller.
ENTHALPY CONTROLLER
RED
BRN
B
TR
TR1
C
A
D
+
SO
+
SR
3
2
GRAY/ORN
1
LED
GRAY/RED
NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside air-
stream.
Fig. 25 --- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
To wire the return air enthalpy sensor, perform the following (See
Fig. 25):
1. Use a 2- -conductor, 18 or 20 AWG, twisted pair cable to
connect the return air enthalpy sensor to the enthalpy
controller.
2. At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the (SR+)
terminal on the enthalpy controller. Connect the BLK wire
to (S) spade connector on the return air enthalpy
and the (SR) terminal on the enthalpy controller.
(OUTDOOR
S
AIR
+
ENTHALPY
BLK
SENSOR)
RED
S
(RETURN AIR
ENTHALPY
+
SENSOR)
WIRE HARNESS
IN UNIT
C06019
sensor
HH57AC078 ENTHALPY
SENSOR (USED WITH
ENTHALPY CONTROL
FOR DIFFERENTIAL
ENTHALPY OPERATION)
Fig. 26 --- Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
WIRING
HARNESS
ACTUATOR
Fig. 27 --- EconoMi$er IV Component Locations
ECONOMI$ER2
PLUG
BAROMETRIC
RELIEF
DAMPER
Fig. 28 --- EconoMi$er2 Component Locations

Optional Economi$er IV and Economi$er2

See Fig. 27 for EconoMi$er IV component locations. See Fig. 28 for
EconoMi$er2 component locations.
34
HH57AC077
ENTHALPY
CONTROL AND
OUTDOOR AIR
BRACKET
ENTHALPY SENSOR
C 7 4 0 0
A 1 0 0 4
MOUNTING PLATE
C06020
ECONOMI$ER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
C06021
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
GEAR DRIVEN
DAMPER
C06022