Carrier 50JS Installation, Start-Up And Service Instructions Manual page 2

Single-package heat pump units
Table of Contents

Advertisement

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
UNIT
ELECTRICAL CHARACTERISTICS
50JS018
208/230-1-60
50JS024
208/230-1-60
50JS030
208/230-1-60, 208/230-3-60
50JS036
208/230-1-60, 208/230-3-60, 460-3-60
50JS042
208/230-1-60, 208/230-3-60, 460-3-60
50JX024
208/230-1-60
50JX030
208/230-1-60,208/230-3-60
50JX036
208/230-1-60,208/230-3-60, 460-3-60
INCHES [mm]
INCHES [mm]
UNIT WEIGHT
lb
283
128.4
289
131.1
287
130.2
291
132.0
323
146.5
299
135.6
320
145.2
328
148.8
Fig. 2—50JS018-042/50JX024-036 Unit Dimensions
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
UNIT HEIGHT
IN. [MM]
"A"
kg
37.02 [940.3]
19.5 [495.3]
39.02 [991.1]
18.5 [469.9]
39.02 [991.1]
19.5 [495.3]
37.02 [940.3]
19.5 [495.3]
37.02 [940.3]
19.5 [495.3]
41.02 [1041.9]
19.0 [482.6]
37.02 [940.3]
20.0 [ 508]
37.02 [940.3]
20.0 [508]
2
INCHES [mm]
CENTER OF GRAVITY
IN. [MM]
X
Y
16.8 [425.5]
15.0 [381.0]
16.8 [425.5]
15.0 [381.0]
17.5 [444.5]
15.0 [381.0]
17.8 [450.9]
13.0 [330.2]
17.8 [450.9]
13.0 [330.2]
18.3 [463.6]
16.0 [406.4]
19.3 [ 489.0]
17.6 [447.0]
19.0 [482.6]
16.5 [419.1]
C99007
Z