Q7055C HONEYWELL METER POINT CONNECT

SPECIFICATIONS

Models:
Q7055C1053 Honeywell Meter Point Connect Model M1.
Q7055C1055 Honeywell Meter Point Connect Model M2.
Electrical Ratings:
Supply Voltage: 24 VAC, 50 to 60 Hz, 24 VDC (external power
supply required).
Power Consumption: 8 VA.
Temperature Ratings:
Operating: 32° F to 122° F (0° C to 50° C).
Storage: -13° F to +185° F (-25° C to +85° C).
Humidity Ratings:
5 to 93% RH, non-condensing.
System Data:
Processor: 32-bit high-speed microprocessor.
Data Transfer: 10/100 Mbit/sec., 802.3 Ethernet.
LAN Interface: 10/100BaseT (RJ-45).
Field Bus: [CH1], [CH1,CH2] RS-485 DC Coupled to M-Bus
level converter.
Device Interface: Serial RS-232.
Memory Type: SDRAM, NOR & NAND Flash.
MTBF: > 100,000 hours.
Safety:
Protection Standard: IP20 according to EN60529.
Protection Class: II according to EN60730-1.
Flame Retardant: V0 according to UL 94.
Dimensions (W x H x D): 8-13/16 in. (224 mm) x 2-13/16 in.
(72 mm) x 7-13/16 in. (199 mm).
Weight: 2.0 lb (0.9 kg).
Approvals:
EN61000-6-4; 2007
EN61000-6-2; 2005
Low Voltage Directive 2006/95/EC
RTTE Directive 1999/5/EC
EMC Directive 2004/108/EC
RoHS Directive 2011/65/EU
WEEE Directive 2002/96/EC
Energy Management Equipment: UL916
FCC Part 15 Class A
Additional Equipment:
Model EMSA240075, P/N EMSA240075-P5P-SZ 120/240
Vac, 50/60 Hz input, 24 Vdc, 0.75 A output, Class 2.
50/60 Hz input, 24 Vdc, 0.75 A output, Class
2, Honeywell part number 50050810-002 (included).
AC Power Supply: 120 Vac 50/60 Hz input, 24 Vac output
50008533-001/U Wall Hanging Accessories Kit.
DC Power supply: CUI Model No. SMI18-24-V-P5, 120/ 240
Vac, 50/60 Hz input, 24 Vdc, 0.8 A output, Class 2.
Accessories
Honeywell Meter Point Connect devices provide RS485 signal
interface for bus connection(s), and require use of level
converter device(s) for conversion of RS485 levels to M-Bus
voltage levels for connection to meters. Following level
converters have been tested for use with MPC devices:
39-00002
RS485 to M-Bus Converters:
Relay Model PW60: RS485 > M-Bus level converter for up to
60 devices.
ADFweb Model HD67022M-20: RS485 > M-Bus level
converter for up to 20 devices.
RS232 TO M-BUS CONVERTERS:
(These are used with RS485 > RS232 converters listed
below)
Relay Model PW3: RS232 > M-Bus level converter for up to 3
devices
Relay Model PW20: RS232 > M-Bus level converter for up to
20 devices
RS485 TO RS232 CONVERTERS:
MOXA Model TCC-108I: RS485 > RS232 converter.
B&B Model 4WSD90TB: RS485 > RS232 converter.
ICS Model I-7520R: RS485 > RS232 converter.
Connecting multiple M-Bus level Converters on MPC
single M-Bus Channel:
MPC M-BUS CH1 or CH2
RS485
M-BUS LEVEL
LC1
CONVERTER
M-BUS SUPPORTED
SUB-METERING DEVICES
Fig. 2. Connecting multiple M-Bus Converters
In order to connect more meters to an M-Bus port than
supported by a single converter device, additional M-Bus
converter(s) can be connected to the RS485 M-Bus on M1 or
M2 devices in parallel with the existing converter. Only the
converters that directly convert between RS-485 and M-Bus
(and do not use an intermediate RS232 type connection) can
be connected in this manner. The end-of-line (EOL)
terminations and biasing for each device connected to the
RS485 M-Bus (CH1 or CH2) as well as the port switch
settings for MPC should be set in accordance with location of
each device on the bus.
2
RS485
RS485
LC1
LC1
M25412A