12-3-3 Outdoor discharge temp. sensor error(OPEN/SHORT)
Outdoor unit display
Indoor unit display
How to determine
Disconnection and short of outdoor discharger temp. sensor
Reason of error
Disconnection or leak of Applied sensor
Does the outdoor discharge
temp. sensor connected to PCB?
(CN42)
Yes
Measure the resistance value
between two terminals after separating
the outdoor discharge temp.
sensor connector from PCB
At this time, Is largely
deviate the resistance value from
side table value?
No
Check the out temp.
sensor is normal or not by use of out
data display part
© Check the temp. data is
normal or not after pressing K4 1 times.
At this time, is occurred the difference
between the out temp. and data?
Yes
Reoperation after PCB replacement
Samsung Electronics
All manuals and user guides at all-guides.com
(Outdoor discharge temp. sensor OPEN/SHORT error)
(Operation)
(Timer)
(Airflow)
No
Yes
Outdoor heat exchanger
temp. is defective(replace)
No
PCB and sensor are normal.
(Filter)
Reoperation
after connect to
connector PCB
To perform the test
operation by use of K2
Troubleshooting
Temp.
Resistance
(˚C)
(kΩ)
130
8.9
120
11.2
100
18.5
80
32
60
59
25
200
20
242
10
362
0
553
12-8