Toshiba RAV-GM2241AT8-E1 Installation Manual page 27

Split type outdoor unit
Table of Contents

Advertisement

Are there scratches or dents
on the existing pipes?
NO
Is it possible to operate the existing
air conditioner?
YES
• After the existing air conditioner is operated in cooling
mode for approx. 30 minutes or longer, recover the
refrigerant.
• Refer to "13 Refrigerant recovery"
• For cleaning the pipes and recovering oil
Was largely discolored oil or a large quantity of
remains discharged? (When the oil deteriorates, the
color of the oil changes to a muddy or black color.)
NO
Connect the indoor/outdoor units to the existing pipe.
Set up SW01 and SW02 for existing piping switch.
(Refer to "13 Existing piping")
• Use a flare nut attached to the main unit for the indoor/
outdoor units. (Do not use the flare nut of the existing
pipe.)
• Re-machine the flare machining size to size for R32.
• (Airtight test), Vacuum dry, Refrigerant charge, Gas
leak check
Test run
51-EN
YES
Existing pipes: Cannot be used.
• Use new pipes.
NO
YES
Clean the pipes or use new pipes.
– 26 –