Mitsubishi Electric CITY MULTI PEFY-P20VMAL Technical & Service Manual page 27

Table of Contents

Advertisement

[ VII Troubleshooting ]
2. Capacity code setting
(1) SW2
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
The switches are set to correspond to the unit capacity.
PEFY-P20VMA(L)-E
PEFY-P25VMA(L)-E
PEFY-P50VMA(L)-E
PEFY-P63VMA(L)-E
PEFY-P100VMA(L)-E
PEFY-P125VMA(L)-E
3. Model setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Please see the WIRING LABEL on the control box.
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory setting
Please see the WIRING LABEL on the control box.
Set SW5 to 240V side when the power supply is 240 volts.
When the power supply is 220 and 230 volts, set SW5 to 220V side.
HWE0812B
PEFY-P32VMA(L)-E
PEFY-P40VMA(L)-E
PEFY-P71VMA(L)-E
PEFY-P80VMA(L)-E
PEFY-P140VMA(L)-E
- 22 -
GB