TR OUB LE S HO O TIN G B LA N K SC RE E N / D I SP L AY
If the VFD's screen / display is blank it usually means the internal 24v power supply is shorted or damaged. In most cases if a
connected circuit is causing the short, disconnec�ng that circuit will restore 24v power to the screen / display.
Check for power on the VFD's L1 and L3 input power terminals.
Disconnect the encoder wires from the VFD's main body control circuit terminals A, B, COM, CM1.
Disconnect all wires from the VFD's main body control circuit terminals related to 24v, (COM, P24, P-, P+, CM2)
Contact Detroit Hoist for further assistance.
TE M P OR AR I LY S W IT C HI N G F RO M C LO SE D LO O P TO O PE N L OO P
In the case of an encoder failure, it might be required to switch from closed loop to open loop in order to lower a load.
DO NOT con�nue to operate the hoist in open loop mode unless for troubleshoo�ng purposes without a load suspended.
Opera�ng a closed loop hoist in open loop mode other than for the purpose of troubleshoo�ng without a load suspended or
lowering a load is HIGHLY DISCOURAGED since all safety features will be disabled.
open loop mode with a load suspended or the load may fall, use other means to remove suspended load.
To switch from closed loop to open loop change parameter AA121 = 08 SLV for high torque output and power cycle the VFD.
No other parameters are required to be changed. All safety func�ons will be bypassed automa�cally, and the encoder limit
func�ons will be ignored. The brake release circuit will be switched over to the open loop brake control using brake release and set
frequencies.
Function
VFD Control Mode
IMPORTANT!
– If an E51 fault was occurring, DO NOT switch to open loop mode with a load suspended or the load may fall, use
12/17/2018
Hitachi P1 Closed Loop Hoist Basic Instruc�on Manual Firmware V19 – V25
Parameters
AA121
other means to remove suspended load.
If an E51 fault was occurring, DO NOT switch to
Value
10: Closed Loop Vector
08: Open Loop SLV
24