Clean And Grease Breaker - ABB Emax 2 Installation And Maintenance Manual

Direct/cic replacement of legacy ge ak 600a - 4000a circuit breakers used in akd-5 & substructures
Table of Contents

Advertisement

Clean and Grease Breaker

Before installing or operating a breaker, refer to the Emax 2 Breaker installation manual
1SDH001330R0002 for pre-operation inspecting and testing.
Check thoroughly for any damaged or loose parts and for any dirt or foreign matter
which may be on the breaker.
Clean those areas if necessary with a clean, lint-free rag and isopropyl alcohol or acetone.
Be sure to apply a thin film of Mobilgrease #28 to the primary disconnect fingers for
better electrical connections on the breaker, and lower racking force.