(1) Mount the holder.
Screws
(3) To remove the remote controller (when use at hand).
Slide up
Pull out

4. FUNCTION SETTING

Perform the "FUNCTION SETTING" according to the installa-
tion conditions using the remote controller.
Entering the function setting mode
While pressing the FAN button and SET TEMP. (
simultaneously, press the RESET button to enter the
function setting mode.
STEP 1
Selecting the remote controller signal code
Use the following steps to select the signal code of the remote
controller. (Note that the air conditioner cannot receive a
signal code if the air conditioner has not
been set for the signal code.)
The signal codes that are set through
this process are applicable only to the
signals in the FUNCTION SETTING.
For details on how to set the signal
codes through the normal process,
refer to 5. SELECTING THE REMOTE
CONTROLLER SIGNAL CODE.
(1) Press the SET TEMP. (
button to change the signal code
between
.
Match the code on the display to the air conditioner signal
code. (initially set to )
(If the signal code does not need to be selected, press the
MODE button and proceed to STEP 2.)
(2) Press the TIMER MODE button and check that the indoor
unit can receive signals at the displayed signal code.
(3) Press the MODE button to accept the signal code, and
proceed to STEP 2.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the
batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code
after replacing the batteries.
If you do not know the air conditioner signal code setting, try
each of the signal codes (
which operates the air conditioner.
(2) Set the remote controller.
Insert
Press in
)
) (
)
) until you fi nd the code
STEP 2
SELECTING THE FUNCTION NUMBER AND SETTING
VALUE
Refer to the indoor unit installation manual for details on the
function numbers and setting values.
Selecting the function number and setting value
(1) Press the SET TEMP. (
function number.
(Press the MODE button to switch between the left and
right digits.)
(2) Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function
number selection.)
(3) Press the SET TEMP. (
setting value.
(Press the MODE button to switch between the left and
right digits.)
(4) Press the TIMER MODE button, and START/STOP
button, in the order listed to confi rm the settings.
(5) Press the RESET button to cancel the function setting
mode.
(6) After completing the FUNCTION SETTING, be sure to
turn off the power and turn it on again.
Function number
After turning off the power, wait 10 seconds or more before
turning on it again.
The FUNCTION SETTING doesn't become effective if it
doesn't do so.
Function details
Function
Functions
number
1) Filter sign
11
2) Ceiling height
20
3) Outlet directions
22
Static
4)
pressure
Cooler room
5)
temperature
30
correction
Heater room
6)
temperature
31
correction
7) Auto restart
40
Indoor room
temperature
8)
42
sensor switching
function
) (
) buttons to select the
) (
) buttons to select the
value
Setting
CAUTION
Compact
Compact
Slim
wall
cassette
duct
mounted
mounted
*1