14. Dip Switch Setting

(1) BM1 introduction
BM1
Indoor searching after
BM1_1
startup
Fan motor quantity
BM1_2
selection
BM1_3
Fan motor selection
Priority selection for energy
BM1_4
saving /effect
Indoor ON / OFF
BM1_5
simultaneous control
Defrosting condition
BM1_6
selection
BM1_7
Defrosting level
BM1_8
Quiet running function
Note:
Either the indoor unit quantity unlocked or the locked quantity is different with actual connecting number,
the unit cannot running.
Definition
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Introduction
Begin to search indoor (DEFAULT)
Stop searching indoor and lock the quantity
Select by model (DEFAULT)
Forced single fan (only 80/112/125/140/160 model use)
AC (DEFAULT)
DC
Energy saving priority (DEFAULT)
Effect priority
Unavailable (default)
Available
Not easy to frost area (default)
Easy to frost area
Ordinary (default)
Strengthen (increase the defrosting time)
Quiet running function is unavailable (default)
Quiet running function is available