The KT-PC4216 is an open collector to 12 VDC 16 zones output module. It can
be used for elevator access control (may require additional hardware).
2.
Specifications
16 outputs low current module, 12V, 50mA max. each, power drawn from
Combus (since Combus can handle a maximum of 500mA, a KT-PC4204
module in "repower" mode can be used to increase the current of the
Combus of 1 Amp)
Connects to KT-300 via 4-wire Combus
Nominal current draw of 15mA (from Combus)
Tamper contact input
Can be used for elevator access control
3.
Installing the KT-PC4216
3.1. Unpacking
The KT-PC4216 package should include the following parts/items:
One (1) KT-PC4216 circuit board
Four (4) plastic standoffs
One (1) installation instructions sheet
3.2. Mounting
The KT-PC4216 should be located inside a compatible cabinet (Kantech part no.
KT-4051CAB), mounted in a dry, secure location. Preferably, it should be placed
at a convenient distance from the connected devices.
Perform the following steps to mount the unit:
1.
Press the four (4) plastic standoffs through the mounting holes at back of
the cabinet,
2.
Secure the cabinet to the wall in the desired location. Use appropriate wall
anchors when securing the cabinet to drywall, plaster, concrete, brick or
other surfaces,
3.
Press the circuit board into the plastic standoffs to secure the module to the
cabinet.
Once the unit is mounted, wiring may be started.
3.3. Installation and Wiring
Before beginning to wire the unit, ensure that all power (AC transformer and
battery) is disconnected from the controller.
Kantech Systems
Tel.: 1 (450) 444 2030 • Toll Free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright  2004 Kantech Systems. All rights reserved • Specifications may change without notice.
Perform the following steps to complete wiring:
1.
Connect the four Combus wires to the KT-PC4216. Connect the red, black,
yellow and green Combus wires to the RED, BLK, YEL and GRN
terminals, respectively.
2.
Complete all output wiring as illustrated below:
Note: Current is drawn from the combus.
Note: May require a KT-PC4204 power supply module if drawing too much
current from the Combus.
3.
Connect the external tamper switch, if used.
Consult the wiring diagrams for further information.
3.4. Applying Power
After all wiring is completed, apply power to the KT-300 controller. Connect the
battery leads to the battery, then connect the AC transformer.
Note: Do not connect the power until all wiring is complete.
KT-PC4216
Output Module
DN1247-0404