Hazardous Voltage.
Hazardous Voltage.
Will cause death or serious injury.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
Turn off and lock out all power supplying this device before
working on this device.
working on this device.
Replace all covers before power supplying this device is
Replace all covers before power supplying this device is
turned on.
turned on.
Hazardous Voltage.
Hazardous Voltage.
Will cause death or serious injury.
Will cause death or serious injury.
Insulate cable and connector to avoid phase to
phase or phase to ground arcing damage.
6
8
Fuse
[ Fusiblee ]

Wire Connector

[ Conexión del cable ]
8 mm
OR
5/16"
TA2JG250PT / 3VL9425-4TF03
Tensión peligrosa.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle servicio.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
energizar el interruptor.
Tensión peligrosa.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Puede causar la muerte o lesiones graves.
Insular cable y conector para evitar daños por
arqueo de fase a fase o a tierra.
10 lb.in.
[ 1.1 Nm
Customer supplied
[ Provisto por Cliente ]
Wire Size
[ Rango Cable ]
[ Clase B ]
Cu / Al
3/0 – 4/0 AWG
[ 95 mm² ]
Cu / Al
250 kcmil
[ 120 mm² ]
7
]
]
Customer supplied
[ Provisto por Cliente ]
Req. UL 486A - 486B
Wire Stranding ( Cable )
[ Hebras ]
CU Only
CU / AL
[ CU Solamente ]
Class B
Class C
[ Clase C ]
19
37
37
61
3 / 5
Tension dangereuse.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Danger de mort ou risque de blessures graves.
Couper l'alimentation de l'appareil et barrer avant de
Couper l'alimentation de l'appareil et barrer avant de
travailler.
travailler.
Remplacez touts les couverts avant que
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
l'approvisionnement de pouvoir soit alimenté.
Tension dangereuse.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Danger de mort ou risque de blessures graves.
Isolez le câble et le connecteur pour éviter un arc
phase à phase ou phase a la terre.
Torque
[ esfuerzo de
Wire Strip Length
torsión ]
[ Quitar ]
D
B
275 lb. in.
[ 31 Nm ]
C
.71"
[ 18 mm ]
1.46"
[ 37 mm ]
806921A01