Remark:
* A disconnect switch may be required. Check the
local code.
** Use a ring tongue terminal in order to connect a
ground wire to terminal.
Power supply 208/230V AC
1phase 2wires 60Hz.
CONNECTING WIRES
• Wire to be AWG22 double insulated, 300 V insulation. Equal to Belden 9407 (for 12-24 V DC).
• Use copper conductors only.
Note:
*1 Wire to be AWG22 double insulated, 300 V insulation. Equal to Belden 9407.
*2 Power supply cable and grounding wire must use copper wire AWG14.
*3 Connect grounding wire with grounding terminal by using a ring tongue solderless terminal.
WARNING:
Use the indoor/outdoor unit connecting wire that meets the Standards to connect the indoor and outdoor
units and fix the wire to the terminal block securely so that no external force is conveyed to the connect-
ing section of the terminal block. An incomplete connection or fixing of the wire could result in a fire.
1 Remove the service panel.
2 Fix the conduit connector to conduit cover with
lock nut then secure it against unit with screws.
3 Fix the conduit cover to the outdoor unit then
secure it with screws.
4 Connect power supply and indoor/outdoor con-
necting wire to the terminal block.
(Leave some slack in wires to allow easier serv-
icing.)
CAUTION:
Use care so as connecting wires do not con-
tact pipes.
WARNING:
• • • • • Be sure to attach the service panel of the outdoor unit securely, otherwise it may result in a fire or an
electric shock from dust or water.
• • • • • Use the indoor/outdoor unit connecting wire that meets the Standards to connect the indoor and outdoor
units and fix the wire to the terminal block securely so that no external force is conveyed to the connect-
ing section of the terminal block. Incomplete connection or fixing of the wire could result in a fire.
• • • • • Be sure to attach the terminal block cover on the both indoor and outdoor units. If the terminal block
cover is incorrectly attached, it may cause a risk of fire or electric shock due to dust or water penetration.
INDOOR UNIT Å
INDOOR UNIT ı
Terminal block
Terminal block
S1S2S3
S1S2S3
Grounding
terminal **
Disconnect switch *
208/230V AC
1phase 60Hz
208/230V AC
1phase 60Hz
DC12-24 V
(Polar)
Grounding
terminal **
S1
S2S3
S1
S2S3
Terminal block
Terminal block
UNIT Å
UNIT ı
L1
L2
OUTDOOR UNIT
Ground
Connect wires to the matching numbers of terminals.

5. INDOOR/OUTDOOR UNITS CONNECTION FINISHING AND

TEST RUN

5-1
TOOLS DEDICATED FOR THE AIR CONDITIONER WITH R410A
REFRIGERANT
Grounding
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
terminal **
R410A tools
Can R22 tools be used?
Gauge manifold
Disconnect switch *
Charge hose
DC12-24 V
Gas leak detector
(Polar)
Torque wrench
Grounding
Flare tool
terminal **
Flare gauge
Vacuum pump
adaptor
Electronic scale for
refrigerant charging
No: Not substitutable for R410A Yes: Substitutable for R410A
5-2
FLARED CONNECTIONS
PIPE LENGTH AND HEIGHT DIFFERENCE
Limits
Pipe length per indoor unit
Total pipe length for multi-system
Height difference
No. of bends per indoor unit
Total No. of bends for multi-system
Refrigerant adjustment ....... If pipe length exceeds 40 m (131 ft.), additional refrigerant (R410A) charge is re-
(The outdoor unit is charged with refrigerant for total pipe length up to 40 m (131 ft.).)
Pipe length
Refrigerant to be added
Grounding terminal
Indoor unit
Conduit
cover
Indoor unit
• For pipe size, see the table below.
Lock nut
Connector
5
Description
No
R410A has high pressures beyond the measurement range of existing gauges.
Hose material and cap size have been changed to improve the pressure resist-
No
ance.
No
Dedicated for HFC refrigerant.
Yes
1/4 and 3/8
No
1/2
Yes
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
New
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use exist-
New
ing vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant
New
bubbles due to high pressure and high-speed vaporization.
2A20NA
25 m (82 ft.)
max.
50 m (164 ft.) max.
10 m (33 ft.)
max.
25
max.
50
max.
quired.
Up to 40 m (131 ft.)
No additional charge is required.
Additional charge is required.
Exceeding 40 m (131 ft.)
(Refer to the table below.)
1.06 oz each 5 ft.
ı UNIT
Outdoor
unit
Å UNIT