Troubleshooting
5.4
Correction procedures
5.4.1
Rebooting the software
In case of configuration data loss or any other file system error that prevents the
IED from working properly, the software can be rebooted. All default settings and
configuration files stored in the factory are restored.
1. Select Configuration > General from the main menu structure.
2. Enable parameter editing by selecting Enable Write
3. Reboot the software by changing the New Value field from Cancel into Activate.
4. Select Write to IED
5.4.2
Restoring factory settings
In case of configuration data loss or any other file system error that prevents the
IED from working properly, the whole file system can be restored to the original
factory state. All default settings and configuration files stored in the factory are
restored.
Restoring factory settings is possible with PCM600.
60
Only a user with System Update right (refer to table Default roles-to-
rights in the Cyber Security Deployment Guideline) can reboot the
software.
For more information, refer to SSC600 Device Management section in
the Engineering Manual.
to save changes into the IED's memory.