Circuit opening overcurrent relay

Advertisement

T Y P E CO CIRCUIT O P EN I NG R E LAY
s tationary contact s houl d have a mimmum of 1 / 3 2"
wip e . The bridgin g moving contact should touch both
stationary contacts simultaneously.
ROUTINE MAINTENANCE
All relays should be inspected periodically and
the time of operation should be checked at least
once every year or at such other time intervals as
may be dictated by experience to be suitable to the
particular application.
Phantom loads should not be
used in testing induction-type relays because of the
resulting distorted current wave form which produces
an error in timing.
All contacts should be periodically cleaned .
tt
contact
burnisher
1 82A836H0 1
for this purpose .
The use of abrasive material for
cleaning contacts is not recommended, because of
the danger of embedding s mall particles in the face
of the soft silver and thus impairing the contact.
CAL I B RAT ION
Use of the following procedure for calibrating the
relay if the relay has been taken apart for repairs or
the adjustments disturbed.
not be used until it is apparent that the relay is n ot
in proper working order. (See "Acceptance Check " )
C O UNIT
1 . CONTACTS
a) By turning the time dial , move the moving con­
tacts until they defl ect th e stationary contact
to a position wh ere the s tationary c ontact is
resting against its backstop. The index mark
l ocated on th e movement frame should coincide
with the "0" mark on the time dia l .
b ) For relay& identified with a "T " , l ocated at
l ower l eft of stationary c ontact bl ock , the index
mark on the movement frame will coincide with
the "0" mark on the time dial when the s tation­
ary contact has moved through approximately
one-hal f
of its normal defl ection. Therefor e ,
with th e s tationary contact resting against the
backsto p , the index mark is offs e t
the
" 0 " mark by approxima tely . 02 0 " . The
placement of the various time dial positions in
line
with the index mark will give operatin g
times as shown on the res pective time-current
curves .
2. MINIMUM TRIP CURRENT
The adjustment of the spring tension in setting
A
is
recommended
This procedure should
to
the right of
the minimum trip current value of the relay i s most
conveniently made with the damping magnet removed.
With the time dial set on "0" , wind up the spiral
spring by means of the spring adjuster until approxi­
m ately 6-3/4 convolutions show.
Set the relay on the minimum tap setting , the
time dial to position 6 .
+ l .Oo/c
Adjust
the control spring tension so that the
moving contact will leave the bac k stop at tap value
current
and will return to the backstop at tap
value current - 1 . 0%.
3 . TIME C URVE CALIBRATION
Install the permanent magnet.
Apply the indicated current p er Table I for per­
manent magnet adjustm ent ( e . g. C0-8, 2 times tap
value) and m easure the operating tim e . Adjust the
permanent magnet keeper until the operatin g time
corresponds to the v alue of Table I .
Apply the indicated current per Table I for the
electromagnet plug adjustment (e . g . C0-8 , 20 times
tap value) and measure the operating tim e .
the proper plug until the operating tim e c orresponds
to the value in Table I .
plug, front view , increas e s the operating time and
withdrawing the right hand plug, front view , decreases
the time. ) I n adjusting the plugs , one plug should b e
screwed i n completely and the other plug run in or
out until the proper operating time has been obtained.
For type C0- 1 1 relay only, the 1 . 3 0 times tap
val ue o perating time from the number 6 time dial posi­
tion is 5 4 . 9 ±5% se cond s . I t is important that the 1 . 30
times tap val u e current be maintained accurately. The
maintaining of this c urrent accurately is necessary
becaus e of the stee pne ss of the s lope of the time­
current characteristic (Fi gure 9 . A 1% variation in
the 1 . 30 times tap value current ( including measurin g
instrument d e viation) will change the nominal opera­
ting time by a pproximately 4%. If the operating time
at 1. 3 times tap val u e is not within these l imits , a
minor adjustment of the control s pring wi ll gi ve the
c orrect operating time without any undue effect on
the minimum p ick-up of the relay. T his check is to
be made after the 2 times tap val ue adjustment has
been compl eted.
Recheck the permanent magnet adjustment.
the
operating time for this calibration point has
changed , readjust the permanent magnet and then
recheck the electromagnet plug adjustment.
I . L . 4 1 · 1 03 E
Adjust
(Withdrawing the left h and
If
1 5

Advertisement

loading

This manual is also suitable for:

C0-5C0-6C0-7C0-8C0-9C0-11