PHASE 2 - TRANSMITTER INSTALLATION
3. TRANSMITTER INSTALLATION
The following examples are standard mounting locations for instrumentation suitable for these main types of applications:
3.1
TRANSMITTER LOCATION
Level measurement with open tanks
1. Mount the transmitter at the same height or below of the
lowest level to be measured.
2. Connect the transmitter to the bottom of the tank.
Pressure or absolute pressure measurement of a tank
1. Place the taps in the upper part of the tank.
2. Mount the transmitter above the elevation of the process
tap.
3. Connect the transmitter to the tank.
Max. Level
Max. Level
Min. Level
Min. Level
gate valve
gate valve
- 7 -