Installing A Dc Power Supply - Cisco Nexus 9272Q Hardware Installation Manual

Nx-os mode switch
Hide thumbs Also See for Nexus 9272Q:
Table of Contents

Advertisement

Replacing Modules
• If you are using n+n power redundancy, there must be a separate power source for each power supply
• There must be an earth ground connection to the chassis that you are installing the replacement module.
Step 1
Holding the replacement power supply with one hand underneath the module and the other hand holding the handle, turn
the power supply so that its release latch is on the right side and align the back end of the power supply (the end with the
electrical connections) to the open power supply slot before carefully sliding the power supply all the way into the slot
until it clicks into place.
If the power supply does not fit into the open slot, turn the module over before sliding it into the open slot.
Note
Step 2
Test the installation by trying to pull the power supply out of the slot without using the release latch.
If the power supply does not move out of place, it is secured in the slot. If the power supply moves, carefully press it all
the way into the slot until it clicks in place.
Step 3
If the DC power cables and a grounding cable are already connected to an electrical connector block, insert the block
into the power receptacle on the power supply.
If the electrical cables have not been connected to the electrical connector block, wire them as described in
V DC Electrical Connector Block, on page
Step 4
Make sure that the other end of the power cable is connected to the appropriate power source for the power supply.
Step 5
If using a DC power source, turn on the circuit breaker for the DC power source connected to the power supply.
Step 6
Verify that the power supply is operational by making sure that the power supply
what the power supply LEDs indicate, see

Installing a DC Power Supply

This topic is for installing the 48-V DC power supply into switch chassis. If you need to install a high voltage
(HVAC/HVDC) power supply, see
You can replace one power supply while the other one provides power to the switch.
Before you begin
• The circuit breaker for the DC power source for the power supply must be turned off.
• The power supply that you are installing must be capable of using the same airflow direction as the fan
• A DC power source must be within reach of the power cable that will be used with the replacement power
installed in the chassis (power sources must be of the same type—do not mix AC and DC power sources
for the same switch). Otherwise, only one power source is required.
Typically, the chassis is grounded by its metal-to-metal connection to a grounded rack. If you need to
ground this chassis by another means, see
40.
Power Supply LEDs, on page
trays installed in the same switch
supply. If you are using n+n power redundancy, there must be a separate power source for each power
supply installed in the chassis (do not mix AC and DC power sources for the same switch). Otherwise,
only one power source is required.
Grounding the Chassis, on page
56.
Installing an HVAC/HVDC Power Supply, on page
Cisco Nexus 9272Q NX-OS Mode Switch Hardware Installation Guide
Installing a DC Power Supply
24.
Wiring a 48
LED is green. For information on
38.
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus n9k-c9272q

Table of Contents