Applications
A.1 Liquids applications
A.1.4

Volume

Notes:
1. Beam should not detect bin bottom.
If this occurs, use range extension parameters (on transceivers where available) to omit
false echoes.
2. Sound beam must be perpendicular to liquid surface.
When mounting the standpipe and flange, you must ensure that the transducer face will
be parallel with the liquid's surface. Refer to Standpipes (Page 38).
40
Main fill level for full calibration. Above this
level erroneous readings will result as level
has entered blanking zone.
'Alternate'
'Preferred'
'Bad'
Tank manufacturer's full level
Beam angle
Span: Corresponds to tank manufac-
turer's empty level
Rise
Tank manufacturer's empty level
Discharge
May require target to obtain empty
reading
Empty level for 'alternate' locations.
Below this level, echo would reflect
away from the transducer.