Table 2: Single Zone High Ef ciency Standard Wall Mount System Electrical Data.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HSV5
1
LS120HSV5
60
1-1/2
LS180HSV5
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Voltage
Range
MCA MOP
(Min. to Max.)
10.0
10.0
208 - 230
187 - 253
13.0
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Compressor Motor
RLA
Compressor
Quantity
Cooling Heating
15.0
1
7.0
15.0
1
7.0
20.0
1
9.6
RLA = Rated Load Amps.
FLA = Full Load Amps.
GENERAL DATA
Electrical
Outdoor Fan Motor
kW
FLA
7.0
0.043
0.4
7.0
0.043
0.4
9.6
0.124
0.25
Indoor
Fan
Motor
FLA
0.4
0.4
0.4
11