Related Parameters - YASKAWA 1000 Series Installation Manual

Ac drive option, analog monitor
Hide thumbs Also See for 1000 Series:

Advertisement

6

Related Parameters

The following parameters are used to set up the drive for operation with the option. Set
parameters as needed. Parameter setting methods can be found in the drive Quick Start
Guide or Technical Manual.
No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor Selection
(391)
F4-02
Terminal V1 Monitor Gain
(392)
F4-03
Terminal V2 Monitor Selection
(393)
F4-04
Terminal V2 Monitor Gain
(394)
F4-05
Terminal V1 Monitor Bias
(395)
F4-06
Terminal V2 Monitor Bias
(396)
F4-07
Terminal V1 Signal Level
(397)
F4-08
Terminal V2 Signal Level
(398)
<1> The drive outputs voltage while this parameter is being adjusted. Voltage levels can be adjusted to match the
specifications of an external meter.
YASKAWA ELECTRIC TOBP C730600 40B 1000-Series Option AO-A3 Installation Manual
Table 5 Related Parameters
Sets the monitor signal for output from terminal V1.
Set this parameter to the last three digits of the
desired U -
monitor. Some U parameters are
available only in certain control modes.
For example, enter "103" for U1-03.
Sets the gain for voltage output via terminal V1,
where 100% equals 10 V output. Terminal output
voltage is limited to 10 V.
Sets the monitor signal for output from terminal V2.
Set this parameter to the last three digits of the
desired U -
monitor. Some U parameters are
available only in certain control modes.
For example, enter "103" for U1-03.
Sets the gain for voltage output via terminal V2,
where 100% equals 10 V output. Terminal output
voltage is limited to 10 V.
Sets the amount of bias added to the voltage output
via terminal V1.
<1>
Sets the amount of bias added to the voltage output
via terminal V2.
<1>
Sets the voltage level for the analog output.
0: 0 to +10 Vdc
1: -10 to +10 Vdc
6 Related Parameters
Description
<1>
Values
Default: 102
(output
frequency)
Range: 000 to 999
Default: 100.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 50.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
21