Four Way Valve Abnormality - Daikin FTKE25BVM Service Manual

Super multi nx c-series
Hide thumbs Also See for FTKE25BVM:
Table of Contents

Advertisement

Troubleshooting
5.15

Four Way Valve Abnormality

EA
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
The liquid pipe thermistor, the outdoor temperature thermistor and the outdoor unit heat
exchanger thermistor are checked to see if they function within their normal ranges in the
Malfunction
operating mode.
Detection
Malfunction
Either of the following conditions occurs 3 minutes after the compressor has started.
Decision
(Outdoor unit heat exchanger temperature – Liquid pipe temperature) < –5°C
Conditions
(Liquid pipe temperature – Outdoor unit heat exchanger temperature) < –5°C
Supposed
Causes
188
1
2
3
4
5
4
1
1
Cooling / dry operation
Heating operation
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Four way valve coil or harness defective
Four way valve defective
Foreign substance mixed in refrigerant
1
Si12-411A
Service Diagnosis