Honeywell H7625A Installation Instructions Manual

Honeywell H7625A Installation Instructions Manual

Wall-mount humidity/temperature sensors

Advertisement

Quick Links

H7625A, H7635A
Humidity/Temperature Sensors
WALL-MOUNT MODELS
APPLICATION
The H7625A, H7635A Wall-Mount Humidity/Temperature
Sensors are universal Relative Humidity transmitters that
can be powered with either a +18 to 36 Vdc or 24 Vac
supply. The sensors use a half-wave bridge rectifier to
convert AC power to a usable DC voltage. The device
also includes a 20K ohm temperature sensor for optional
use.
The humidity sensors are designed with a field selectable
4 to 20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output signal
equivalent to 0 to 100% RH. All units are shipped from
the factory with a default setting to accept AC power with
three-wire, 0 to 10 Vdc loop-powered output.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
INSTALLATION INSTRUCTIONS
CAUTION
Equipment Damage Hazard.
Improper wiring can damage the sensor
beyond repair.
Follow the wiring instructions carefully.
Location
Install the device where it cannot be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the device.
Mounting
The housing base mounts over standard 2 in. x 4 in.
single gang junction box or flush to the wall:
1. Install the sensor about 5 ft (1.5m) above the floor
in an area with good air circulation at average
humidity and temperature. (See Fig. 1.)
2. Ensure the device receives adequate airflow.
3. Wire the device. (See Fig. 4 through 3.)
4. Ensure proper DIP switch settings.
5. Apply power to the unit.
6. Snap the cover into position.
7. Turn out the 1/16 in. allen screws at the bottom of
the enclosure until the cover cannot be removed.
NO
NO
Fig. 1. Typical sensor location.
YES
NO
5 FEET
(1.5 METERS)
62-0208—3
M4823A

Advertisement

loading

Summary of Contents for Honeywell H7625A

  • Page 1 INSTALLATION INSTRUCTIONS APPLICATION CAUTION Equipment Damage Hazard. The H7625A, H7635A Wall-Mount Humidity/Temperature Improper wiring can damage the sensor Sensors are universal Relative Humidity transmitters that beyond repair. can be powered with either a +18 to 36 Vdc or 24 Vac Follow the wiring instructions carefully.
  • Page 2 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS Output Settings (Table 1) Table 1. Controller Compatibility and Output Settings. The board has three switch blocks: — A six DIP switch block. Required 4-Switch Block Blue and Sensor Settings White — A four DIP switch block.
  • Page 3 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS OUTDOOR HEAT T7770 REMOTE SENSOR SENSOR RELAY 2 DISCHARGE COMPRESSOR COMPRESSOR CONTACTOR 4 CONTACTOR 2 SENSOR T7350 SUBBASE W3/Y4 Y3 COMPRESSOR CONTACTOR 3 HEAT MOTION RELAY RELAY 1 SENSOR HUMIDITY SENSOR COMPRESSOR CONTACTOR 1 ECONOMIZER (HOT) POWER SUPPLY.
  • Page 4 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS CHECKOUT Converting Output Signal to Percent RH CAUTION Equipment Damage Hazard. 4 to 20mA Signal Can short electric circuitry. • Never connect 120 Vac to the transducer. 〈 〉 signal [in mA] 4 – • Connect only DC voltage to a transducer...
  • Page 5 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS APPENDIX RH Test and Configuration DIP Switch Settings (Table 4) 0% RH Output (for Testing Only) IMPORTANT • Only adjust these switches for troubleshooting or Transmitter always outputs a signal of 4 mA or 0 Vdc. The •...
  • Page 6 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS CALIBRATION Using Calibration Trim Potentiometers All transducers are factory calibrated to meet/exceed published specifications. Field adjustment should not be necessary. IMPORTANT IMPORTANT • Due to the sensitive nature of humidity • Do not verify comparative RH with a sling calibration, adjusting trimmer potentiometers psychrometer.
  • Page 7 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS 62-0208—3...
  • Page 8 H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS ® LonSpec™ is a trademark of Echelon Corporation. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark ©...