Vector TLC3-FCR-M2-24 Engineering Manual

Vector TLC3-FCR-M2-24 Engineering Manual

Programmable pid fan coil controller
Hide thumbs Also See for TLC3-FCR-M2-24:

Advertisement

Quick Links

TLC3-FCR-M
Programmable PID Fan Coil controller
Features
Proven PID controls algorithm reduces room temperature
fluctuations and energy consumption
Low power energy consumption: < 1W per unit
Temperature control for 2- and 4-pipe fan coil systems.
Automatic fan control for three stage fans.
Cost saving option with Economy functionality and set point
limitations
Control for modulating heating, cooling and fan only operation
modes
Password protected programmable user and control parameters
Setpoint range limitation
o
Access control for setpoints, fan speeds and mode change
o
Access control for heat/cool change and time programs
o
Select your display contents
o
Selectable behavior after return from power failure
o
Temperature display in Celsius or Fahrenheit
Deluxe Version:
Clock and time schedule functions with power failure protection
Blue backlight for LCD
Infrared remote controller option:
With special features for Boost and delayed switching on or off
Applications
Air Only Systems:
Constant or Variable Air Volume systems with three stage fans for single or dual duct systems
o
Air/Water Systems:
Fan Coil units for 2-pipe or 4-pipe systems
o
radiator control, chilled ceiling
o
Simple individual room control for hotel rooms, meeting rooms, etc.
PID-Control of up to 2 modulating valves for heating and cooling
General Description
The TLC3-FCR-M is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-M2 is designed for
2-pipe modulating fan coil systems and features 1 NTC temperature sensor input, one external passive input for
temperature or open contact, three binary outputs (Relays) and one analog output (0-10VDC).
The TLC3-FCR-M4 is designed for 4-pipe modulating fan coil systems and features 1 NTC temperature sensor input,
three binary outputs (Relays) and two analog outputs (0-10VDC) for heating and cooling.
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-M can be
configured using the standard operation terminal. No special tools or software is required.
Ordering
Item Name
TLC3-FCR-M2-24
TLC3-FCR-M2-24-W01
TLC3-FCR-M2-230
TLC3-FCR-M2-230-W01
TLC3-FCR-M2-D-24
TLC3-FCR-M2-D-24-W01
TLC3-FCR-M2-D-230
TLC3-FCR-M2-D-230-W01
TLC3-FCR-M4-24
TLC3-FCR-M4-230
TLC3-FCR-M4-D-24
TLC3-FCR-M4-D-230
Selection of fans
Do not directly connect devices that exceed 2A. Observe startup current on inductive loads! Do not connect more than
one fan coil unit to one controller.
Modulating Actuators:
Choose actuators with an input signal type of 0-10V DC or 2-10V DC. Observe maximal signal current of 1mA!
Doc: 70-00-0181, V3.0 Date: 20120424
Subject to alteration
Item code
Variant
40-10 0131
Standard
40-10 0131-01
Cooling only
40-10 0100
Standard
40-10 0100-01
Cooling only
40-10 0136
Deluxe
40-10 0136-01
Cooling only
40-10 0101
Deluxe
40-10 0101-01
Cooling only
40-10 0132
Standard
40-10 0104
Standard
40-10 0137
Deluxe
40-10 0105
Deluxe
© Vector Controls GmbH, Switzerland
TLC3-FCR-M Engineering Manual
Power
Features
24VAC/DC
Fan coil controller with:
230VAC
1 TI int, 1 external input
3 DO (Relay) Fan control
24VAC/DC
1 AO (0-10VDC) PID valve control
230VAC
24VAC/DC
1 TI int
230VAC
3 DO (Relay) Fan control
24VAC/DC
2 AO (0-10VDC) PID valve control
230VAC
Page 1

Advertisement

loading

Summary of Contents for Vector TLC3-FCR-M2-24

  • Page 1 Modulating Actuators: Choose actuators with an input signal type of 0-10V DC or 2-10V DC. Observe maximal signal current of 1mA! Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 1 Subject to alteration...
  • Page 2: Technical Specification

    60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.) Distance for mounting screws: Horizontal and vertical: 45 to 63mm (1.8 to 2.5 in.) Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3 0…10 V DC TLC3-FCR-M4: Signal common: Common 0 potential for inputs and analog outputs. Analog cooling output: 0…10 V DC Analog heating output: 0…10 V DC Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    The output is switched off. Verify parameter settings and wiring. Steady: Frost protection is active. Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5 A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined.  See chapter operation, advanced settings for instructions on how to set the time. Access to time schedules may be disabled with UP-04  Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6 Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The mode change may be disabled using the UP parameters. Note: The remote controller is currently only available in °C mode. Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7 The unit will switch automatically back to the scheduled mode when the reset time expires. = Reset of override mode is not active. 1…255 = delay in minutes to switch off device Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration...
  • Page 8: Control Configuration

    Depending on the room size and heating / cooling equipment used a value between 0.1 and 1.5 should be sufficient. Below are suggested values: Heating: K : 0.1-0.5 Cooling: K : 0.3-0.8 Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9 Dry contact: Heating if contact closed FC21 > FC22 25°C (77F) 15°C (59F) Dry contact: Cooling if contact closed FC21 < FC22 15°C (59F) 25°C (77F) Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 TLC3-FCR-M Engineering Manual Notes: Doc: 70-00-0181, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...