Further details regarding the individual steps
3. Pull electrical cables from fan motor
A, gas valve B, ionisation elec-
trode C, ignition unit D and earth
tab E.
4. Release gas supply pipe fitting F.
Checking the burner gasket and the burner gauze assembly
Check burner gasket A and burner gauze assembly E for damage and replace, if
required.
B
Commissioning, inspection, maintenance
5. Release four nuts G and remove the
burner.
!
F
E
(cont.)
Please note
Prevent damage to the wire
gauze.
Never rest the burner on the
gauze assembly.
3x
D
A
C
35