36 | Troubleshooting

TROUBLESHOOTING

Unit Troubleshooting

NOTICE: If troubleshooting a system that is
low on refrigerant due to a system leak, do
not simply add refrigerant. The leak must be
found and repaired per F-Gas regulation.
Problem
Cooling
X
NO
COMPRESSOR
OPERATION
BUT FAN RUNS
X
8733829041 (2021/07)
Unit Troubleshooting
Mode
Check
Heating
Is the Fault
LED
blinking one
(1) time?
Is the Fault
LED
X
blinking one
(1) time?
Is the Fault
LED
blinking two
(2) times?
Subject to change without prior notice
Possible
Cause
High
Check water valves and/or pumps for
pressure
proper operation. Check for water coil
fault—no or
blockage.
low water
flow
High
Check water temperature—is it in
pressure
range?
fault—high
water
temperature
High
Check for proper flow rate and water
pressure
temperature, but low-water-side temp
fault—fouled
rise in cooling.
or scaled
water coil
Check the fan motor for proper
operation.
High
pressure
Check the air filter.
fault—No or
Inspect the air coil for dirt/debris.
low air flow
Check duct work—Are dampers closed
or blocked?
Check the fan motor for proper
operation.
Check the air filter.
Low pressure
fault—No or
low air flow
Inspect the air coil for dirt/debris.
Check duct work—Are dampers closed
or blocked?
Low pressure
Check refrigerant pressure with a
fault—Low
gauge set.
refrigerant
QV Series Heat Pumps
Action
QV Series Heat Pumps