Purging The Heating Installation; Filling And Purging The Domestic Hot Water System; Checking And Adjusting The Gas Setting - Vaillant atmoTEC exclusive Installation And Maintenance Instructions Manual

Hide thumbs Also See for atmoTEC exclusive:
Table of Contents

Advertisement

7 Start-up
1
4.
Undo the cap on the automatic air vent (1).
Rotations: 1 ... 2
5.
Hinge the electronics box upwards.
6.
Select check programme P. 6.
Check programmes (→ Page 34)
7.
Open all of the thermostatic radiator valves and, if re-
quired, the service valves.
8.
Open the filling device that is installed on-site.
9.
Fill it with water until the required system pressure is
shown on the manometer and/or in the display.
7.5

Purging the heating installation

1.
Select check programme P. 0.
Check programmes (→ Page 34)
2.
Make sure that the filling pressure of the heating install-
ation does not fall below the minimum filling pressure.
≥ 0.1 MPa (≥ 1.0 bar)
3.
Check whether the filling pressure of the heating install-
ation is at least 0.02 MPa (0.2 bar) above the counter-
pressure of the expansion vessel ("Exp") (P
P
+ 0.02 MPa (0.2 bar)).
Exp
Result:
Filling pressure for the heating installation is too low
Fill the heating installation. (→ Page 19)
4.
If there is still too much air in the heating installation
at the end of check programme P. 0, repeat the check
programme.
7.6
Filling and purging the domestic hot water
system
Applicability: Product with integrated hot water generation
1.
Open the cold-water isolation valve on the product and
all the hot water draw-off valves.
2.
Fill the domestic hot water system until water escapes.
The domestic hot water system is filled and purged.
3.
Check all of the connections and the entire domestic
hot water system for leaks.
20
7.7
7.7.1
The product's combustion has been tested at the factory and
preset for the gas type indicated on the data plate.
Check the information about the gas type indicated on
the data plate and compare this with the gas type avail-
able at the installation site.
Conditions: The product design is not compatible with the local gas
group
Do not start up the product.
For the gas conversion, use a conversion set (with con-
version instructions).
If possible, carry out a gas conversion for the product, as
described in the conversion instructions.
Conditions: The product design is compatible with the local gas group
Proceed as described below.
7.7.2
1.
Close the gas stopcock.
Installation
2.
Hinge the electronics box downwards.
Installation and maintenance instructions atmoTEC exclusive, atmoTEC plus 0020214272_04

Checking and adjusting the gas setting

Checking the factory-set gas setting
Checking the gas connection pressure (gas
flow pressure)
Caution.
Risk of material damage and operating
faults caused by incorrect gas connection
pressure.
If the gas connection pressure lies outside
the permissible range, this can cause operat-
ing faults in and damage to the product.
Do not make any adjustments to the
product.
Do not start up the product.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents