ROUGH-IN DIMENSIONS
TABLE 1: GAS AND ELECTRICAL CHARACTERISTICS
Manifold Pressure
Model
Type of Gas Inches W.C. kPa
GW/GB-1000
thru 2500
NATURAL
GW/GB-1000
thru 2500
PROPANE
All Models - Maximum Supply Pressure: 14.0 In. W.C. (3.49 kPa)
Minimum Supply Pressure Natural Gas: 6.0 In. W.C. (1.22 kPa)
Minimum Supply Pressure Propane Gas: 11.0 In. W.C. (2.74 kPa)
Minimum Pressures must be maintained under both load and no load
(static and dynamic) conditions.
TABLE 2. ROUGH - IN DIMENSIONS
Model
Inches
GW/GB-1000
GW/GB-1300
GW/GB-1500
GW/GB-1850
GW/GB-2100
GW/GB-2500
BTU/Hr.
Model
Natural Gas Natural Gas Propane Gas Propane Gas
GW/GB-1000
990,000
GW/GB-1300
1,300,000
GW/GB-1500
1,500,000
GW/GB-1850
1,850,000
GW/GB-2100
2,100,000
GW/GB-2500
2,490,000
TOP VIEW
FRONT VIEW
Electrical Characteristics
Volts/Hz
3.5
0.87
120/60
10
2.49
120/60
A
B
c m
Inches
c m
14.1
35.8
12.2
31.0
24.8
63.0
12.2
31.0
30.2
76.7
12.2
31.0
27.7
70.4
11.2
28.4
31.0
78.7
11.2
28.4
38.1
96.8
10.5
26.7
Input
KW
BTU/Hr.
289.95
990,000
380.74
1,300,000
439.31
1,500,000
541.82
1,850,000
615.04
2,100,000
729.26
2,490,000
Refer to "Installation Clearances" section of manual
(page 7) for recommended service clearances prior
to boiler placement.
Amperes
30
30
Figure 1.
C
D
Inches
c m
Inches
40.3
102.4
31.6
40.3
102.4
31.6
40.3
102.4
31.6
43.0
109.2
32.3
43.0
109.2
32.3
43.0
109.2
32.3
Exhaust
KW
Vent Diameter
Inches
c m
289.95
10
25.4
380.74
12
30.5
439.31
12
30.5
541.82
14
35.6
615.04
14
35.6
729.26
16
40.7
2
IMPORTANT!
LEFT SIDE
REAR VIEW
E
c m
Inches
c m
Inches
80.3
26.0
66.0
46.8
80.3
39.3
99.8
57.3
80.3
44.6
113.3
64.3
82.0
44.0
111.8
78.3
82.0
49.5
125.7
85.3
82.0
56.5
143.5
99.3
Inlet
Vent Diameter
Water Conn. Gas Inlet
Inches
c m
8
20.3
10
25.4
10
25.4
10
25.4
12
30.5
12
30.5
F
c m
118.9
145.5
163.3
198.9
216.7
252.2
Size
2 1/2 NPT
2 NPT
2 1/2 NPT
2 NPT
2 1/2 NPT
2 NPT
2 1/2 NPT
2 1/2 NPT
2 1/2 NPT
2 1/2 NPT
2 1/2 NPT
2 1/2 NPT