Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Filter display delay timer 0000: None
01
Dirty state of filter
02
Central control address 0001: No.1 unit
03
Specific indoor unit
04
priority
Heating temp shift
06
Existence of [AUTO]
0d
mode
Cooling only
0F
10
Type
Indoor unit capacity
11
12 Line address
13 Indoor unit address
Group address
14
Louver type
19
(Air direction adjustment)
Temp difference of
[AUTO] mode selection
1E
COOL → HEAT,
HEAT → COOL
Automatic restart of
28
power failure
Selection of option/Trouble
2A
input (TCB-PCUC1E-1: CN3)
HA terminal (CN61)
2E
select
31 Ventilating fan control
32 TA sensor selection
33 Temperature unit select 0000: °C (at factory shipment)
High-ceiling adjustment
5d
(Air flow selection)
Timer setting
60
(wired remote controller)
77 Dual set point
b3 Soft cooling
Occupancy sensor/
b5
Wireless A-B selection
Provided/None
Occupancy sensor
Enable/Invalid
b6
(Absence time judgment
time)
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
to
0099: Unfixed
0000: No priority
0000: 0 °C
0002: +2 °C
to
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0014 : Compact 4-way Cassette
0000: Unfixed
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit of group
0000: No louver
0004: (4-way Air Discharge Cassette type)
0000: 0 deg
to
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0000: None
0000: Filter input
0002: None
0000: Usual
0002: Fire alarm input
0000: Unavailable
0000: Body TA sensor
SET
Type
DATA
0000
Standard (factory default)
0001
High-ceiling (1)
0003
High-ceiling (3)
0000: Available (can be performed) 0001: Unavailable
0000: Unavailable
0000: Unavailable
0000: None
0002: Wireless remote controller provided
0000: Invalid
0002: 60min.
0005; 150min.
Description
0001: 150H
0003: 5000H
0064: No.64 unit
0001: Priority
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Header unit of group
0001: Swing only
0010: 10 deg
0001: Restart
0001: Alarm input (Air washer, etc.) 0002: None
0001: Leaving-ON prevention control 0000: Usual
0001: Available
0001: Remote controller sensor
0001: °F
RM30
RM40
2.7 m or less
2.9 m or less
3.2 m or less
3.5 m or less
(cannot be performed)
0002: Available
0001: Available
0001: Occupancy sensor provided 0000: None
0001: 30min.
0004; 120min.
– 78 –
At shipment
0002 : 2500H
0000: Standard
0099: Unfixed
0000: No priority
0002 : +2°C
0001: Not provided
0000: Heat pump
0014 : Compact
4-way Cassette
According to capacity
type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0004: (4-way Air
Discharge Cassette
type)
0003: 3 deg
(Ts ±1.5)
0000: None
(HA terminal)
0000: Unavailable
0000: Body TA sensor
0000: °C
0000: Standard
RM56
3.2 m or less
3.4 m or less
3.5 m or less
0000: Available
0000: Unavailable
0001: Available
0002: Enable
(60 min.)