Toshiba RAV-GM2241AT8-TR Service Manual page 77

Air-conditioner split type
Table of Contents

Advertisement

No.
Parts name
1
Compressor
(Model : RX640A3F-21M)
2
Outdoor fan motor
(Model : ICF-340-A100-1)
3
4-way valve coil
(Cooling/heating switching)
(Model : STF-H01AJ1736A1)
4
2-way valve coil
(Model : VPV-M0AJ510B0)
5
PMV coil
(Model : PQM10441)
Table Inspection of outdoor unit main parts
Measure the resistance value of each winding by using the tester.
Red
White
Measure the resistance value of each winding by using the tester.
Red
White
Measure the resistance value of each winding by using the tester.
Connector : White
Measure the resistance value of each winding by using the tester.
Connector : White
Measure the resistance value of each winding by using the tester.
Position
Red – White
Red – Orange
Gray – Yellow
Gray – Blue
Checking procedure
Position
Red – White
White – Black
Black
Black – Red
Position
Red – White
White – Black
Black
Black – Red
Resistance value
46 ± 3.7 Ω
46 ± 3.7 Ω
46 ± 3.7 Ω
46 ± 3.7 Ω
– 77 –
Resistance value
0.56 ± 0.04 Ω
Under 20°C
Resistance value
18.86 ± 1.9 Ω
Under 20°C
Resistance value
1725 ± 172.5 Ω
Under 20°C
Resistance value
1435 ± 144 Ω
Under 20°C
Under 20°C